【 Weak current College 】 Gulf equipment technical characteristics and parameters
Table of contents
(A) fire alarm controller 1
● JB-QT-GST5000 type control center fire auto-alarm host 1
● JB-QG-GST5000 type Control Center 3 automatic fire alarm host
● JB-QB-GST500-type fire alarm controller (linkage) 5
● JB-QB-GST200-type fire alarm controller (linkage) 7
(Ii) fire detector 9
● JTY-GD-G3 type intelligent photoelectric smoke detector 9
● JTW-ZCD-G3N type intelligent electronic differential fixed temperature heat detector 11
● JTY-GF-GST104-non-coding photoelectric smoke detector 12
● JTWB-ZCD-G1 (A) non-encoded electronic differential fixed temperature heat detector 12
● BT-KVA001 coding combustible roof household 13
● BT-KVA002 coding combustible wall-mounted home 14
● JTY-HS-G2-smart style infrared beam smoke detector 15
● JTW-LDB-100 type intelligent cable type heat detector 16
● JTG-ZW-G1-smart 17 UV flame detector
● JTF-GOM-GST601 type intelligent gas temperature composite detector 18
● JTGB-ZM-GST501/I/I-type explosion-proof 19 UV flame detector
(3) alarm buttons 20
● J-SAP-8401-manual fire alarm buttons 20
● J-SAP-8402-manual fire alarm button (with the phone jack) 21
● LD-8403-intelligent code 22 fire hydrant alarm button
● LD-8404 type intelligent encoding fire hydrant alarm button 23
(4) onsite module and interface device 24
● LD-8300-monitoring module 24
● LD-8301-Smart encoding for single-input/single-output module 25
● LD-8303 intelligent encoding two-input/output modules-26
● LD-8304 coding fire phone module 27
● LD-8305 coding fire radio switch module 27
● LD-8311-bus 28 relay fiber interface
● LD-8313-bus isolator 29
● LD-8319 coding repeaters 30
● LD-8320 active Terminal 31
(5) fire displays disc 32
● ZF-101 fire displays disc 32
● ZF-500 type Chinese character LCD display disk 33 fire
● ZF-GST8903-graphical fire show tray 34
(6) power 35
● GST-DY-100-type power supply box 35
● GST-DY-200 type intelligent power supply unit 36
● GST-LD-D02-intelligent power plate 37
(VII) fire broadcasting system 38
• Bus system fire emergency broadcasting system 38
«More wire fire emergency broadcasting system is 39
(8) fire telephone system 40
• Bus system fire telephone system 40
«More wire fire telephone system 41
(9) 42 gas fire control
● LD-QKP06 type gas fire extinguishing control plate 42
● Gas extinguishing control card 43
● LD-8317A-gas spray led 44
● LD-8318A-emergency stop-button start/45
(10) many wire linkage control device 46
● KZK-100-multiple wire control card 46
● LD-KZC-100-multi-line system CPU control card (spare) 47
● LD-8302C type conversion interface module 48
(11) other devices 49
● GST-HX-M8501/GST-HX-M8502 coding fire alarm sound/49
● BMQ-1 electronic encoder 50
● GST-5000 color CRT display system 51
Equipment performance characteristics
GST licensing distribution intelligent fire alarm and fire control system is the Hudson Bay Company successfully developed high-tech fire electronic products, the technology mature, their performance characteristics are as follows:
(A) fire alarm controller
● JB-QT-GST5000 type control center fire auto-alarm host
Design uses JB-QT-GST5000 type Chinese character LCD display fire alarm controller (linkage) as the control center alarm controller, its main characteristics are as follows:
Big-screen liquid crystal display Chinese characters, various alarm status information can be intuitive to Chinese characters are displayed on the screen to make it easy for users to use; you can observe the work of an intelligent dynamic probes for curve for the scene of actual environmental conditions; controller with powerful Panel control and operating functions, a variety of feature comprehensive, simple and convenient.
The controller has a modular design, highly intelligent features, together with the smart probe composition distribution intelligent fire alarm systems, systems of work high reliability and greatly reduces false positives.
System internal parallel bus dataTransport, the main control board and the circuit board for information transmission between a query, it would not affect multiple loop machine inspection speed, fast, accurate information transmission.
All bus control system wiring flexibility, you can use alarm point and linkage point total circuit wiring, wiring simple; you can also use alarm point and linkage dotted circuit wiring methods, systems, and high reliability.
The controller has a very strong field programming capability, the circuit cross-linkage between devices, various Chinese character information note, bus system control devices and much line control devices, such as the linkage between can live programming.
The controller can be completed automation and manual control of the external fire-fighting equipment, which is charged with manual control mode with direct manual control of the output and the encoding key combinations manually control output method, any address within the code point can be occupied by a variety of encoding detector or by the use of various encoding module, design flexibility. Linkage control equipment use 24V DC power supply, making interaction device failure will not affect the normal work of the host.
The main technical indicators are as follows:
◎ LCD size: 320 × 240 graphic dot matrix, you can display Chinese characters 12 rows
◎ Controller capacity:
A. system capacity expanded to 40 block 242 address coding circuit for a maximum capacity of 9680 addresses coding points.
B. external 64 fire show up; interconnection maximum 32-other types of controller.
C. multiple wire control points and direct manual control can bus requires configuration.
◎ Wire:
A. controller and detector using polarity signal second bus connections, and each kind of control modules in addition to the promise of 2 bus out, plus two DC24V power bus.
B. and the other type of controller using polar II bus connection, fire warning shows up, plus two DC24V power bus.
C. color CRT system uses four-core flat telephone line connection through RS-232 standard interfaces, maximum length should not exceed 15m connector.
◎ Using environment: temperature: 0 ° c ~ + 40 ° c relative humidity ≤ 95%, no condensation
¡Ò main power for power: AC 220V; preparation of power to the controller 24Ah sealed lead battery DC24V; linkage by electron DC24V 24Ah sealed lead batteries.
◎ Power consumption ≤ 150W
◎ Dimensions: 1080mm×1113mm×1350mm
◎ Bus communication distance 1.5 km
◎ Have RS-232, and RS-485 interface
● JB-QG-GST5000 type control center fire auto-alarm host
Design uses JB-QG-GST5000 type Chinese character LCD display fire alarm controller (linkage) as the control center alarm controller, its main characteristics are as follows:
Big-screen liquid crystal display Chinese characters, various alarm status information can be intuitive to Chinese characters are displayed on the screen to make it easy for users to use; you can observe the work of an intelligent dynamic probes for curve for the scene of actual environmental conditions; controller with powerful Panel control and operating functions, a variety of feature comprehensive, simple and convenient.
The controller has a modular design, highly intelligent features, together with the smart probe composition distribution intelligent fire alarm systems, systems of work high reliability and greatly reduces false positives.
System internal parallel bus data transfer, the main control board and the circuit board for information transmission between a query, it would not affect multiple loop machine inspection speed, fast, accurate information transmission.
All bus control system wiring flexibility, you can use alarm point and linkage point total circuit wiring, wiring simple; you can also use alarm point and linkage dotted circuit wiring methods, systems, and high reliability.
The controller has a very strong field programming capability, the circuit cross-linkage between devices, various Chinese character information note, bus system control devices and much line control devices, such as the linkage between can live programming.
The controller can be completed automation and manual control of the external fire-fighting equipment, which is charged with manual control mode with direct manual control of the output and the encoding key combinations manually control output method, any address within the code point can be occupied by a variety of encoding detector or by the use of various encoding module, design flexibility. Linkage control equipment use 24V DC power supply, making interaction device failure will not affect the normal work of the host.
The main technical indicators are as follows:
◎ LCD size: 320 × 240 graphic dot matrix, you can display Chinese characters 12 rows
◎ Controller capacity:
A. system capacity expanded to 40 block 242 address coding circuit for a maximum capacity of 9680 addresses coding points.
B. external 64 fire show up; interconnection maximum 32-other types of controller.
C. multiple wire control points and direct manual control can bus requires configuration.
◎ Wire:
A. controller and detector using polarity signal second bus connections, and each kind of control modules in addition to the promise of 2 bus out, plus two DC24V power bus.
B. and the other type of controller using polar II bus connection, fire warning shows up, plus two DC24V power bus.
C. color CRT system uses four-core flat telephone line connection through RS-232 standard interfaces, maximum length should not exceed 15m connector.
◎ Using environment: temperature: 0 ° c ~ + 40 ° c relative humidity ≤ 95%, no condensation
¡Ò main power for power: AC 220V; preparation of power to the controller 24Ah sealed lead battery DC24V; linkage by electron DC24V 24Ah sealed lead batteries.
◎ Power consumption ≤150W
◎ Dimensions: 580mm×520mm×1873mm
◎ Bus communication distance 1.5 km
◎ Have RS-232, and RS-485 interface
● JB-QB-GST500-type fire alarm controller (linkage)
Area alarm controller adopts JB-QB-GST500 type Chinese character LCD display fire alarm controller (linkage), the controller is a maximum capacity of scalable to second circuit of 242 coding points, the main features of the controller as follows:
Big-screen liquid crystal display Chinese characters, various alarm status information can be intuitive to Chinese characters are displayed on the screen to make it easy for users to operate the use.
Controller design highly intelligent, and intelligent probes together composition distribution intelligent fire alarm system, greatly reduce false positives and improve system reliability.
Fire alarm and fire control can be separated by more machines, minutes bus circuit design or stand-alone total bus circuit design, at the same time controller design with short-term, breakage detection and fault alarm function of multiple wire control output point is designed for control of fan, water pump, and other important equipment, can meet the design requirements.
The controller can be completed automation and manual control of the external fire-fighting equipment, which is charged with manual control mode with direct manual control of the output and the encoding key combinations manually control output method, any address within the code point can be occupied by a variety of encoding detector or by the use of various encoding module, design flexibility. Considering that the controllers themselves power system capacity is lower, when the controller receives a charged device, additional settings DC24V power system.
The controller has a very strong field programming capability, the circuit cross-linkage between devices, various Chinese character information note, bus system control devices and much line control devices, such as the linkage between can live programming.
Controller external fire alarm display trays and color CRT display system and other equipment, to meet a variety of system configuration requirements.
Controller with powerful Panel control and operating functions, you can observe a dynamic work curve, the detector features set of comprehensive, simple and convenient.
The main technical indicators are as follows:
◎ LCD size: 320 × 240 graphic dot matrix, you can display Chinese characters 12 rows
◎ Controller capacity:
A. you can take second 242 address coding points loop, a maximum capacity of 484 addresses coding points.
B. external 64 fire show up; interconnection maximum 32-other types of controller.
C.64 direct manual operation bus system control points.
D. maximum configurable 12 more wire control points.
◎ Wire:
A. controller and detector using polarity signal second bus connections, and each kind of control modules in addition to the promise of 2 bus out, plus two DC24V power bus.
B. and the other type of controller using polar II bus connection, fire warning shows up, plus two DC24V power bus.
C. color CRT system uses four-core flat telephone line connection through RS-232 standard interfaces, maximum length should not exceed 15m connector.
◎ Using environment: temperature: 0 ° c ~ + 40 ° c relative humidity ≤ 95%, no condensation
¡Ò main power for power: AC 220V, built-in DC24V 10Ah sealed lead batteries be electro
◎ Power consumption ≤ 50W
◎ Dimensions: 500mm×700mm×170mm
● JB-QB-GST200-type fire alarm controller (linkage)
Design uses JB-QB-GST200 type Chinese character LCD display fire alarm controller (linkage) as area alarm controller, wall-mounted structures, whose main characteristics are as follows:
The controller is a small number of products, there are a variety of configuration options.
Whether the linkage class or alarm class bus devices, controllers are equipped with non-power backup, ensure system debugging completes registration to all of the equipment being monitored.
The controller at post, not only automatically detects the native device (led, function keys, etc.) and also one of detected external device registration information and joint formula information, such as information changes the system will display this information and make the appropriate treatment.
The controller can be configured with up to 10 road more wire control module, and have the output line circuit, short circuit and device failure alarm function, these detection feature can maximize security control module itself and its connection with important device reliability.
The controller on the special importance of gas spray equipment provides independent control of password and the linkage of programming space, and a corresponding sound and light indicates, that gas sprays device is a more stringent monitoring.
This controller can add fire alarm display trays and color CRT display system and optional manual disk and much line control cards and other equipment, to meet a variety of system configuration requirements.
This controller has powerful Panel control and operating functions, you can observe the smart probe dynamic work curve, various function set of comprehensive, simple and convenient.
The controller uses the entire die in structure, beautiful appearance.
The main technical indicators are as follows:
◎ LCD size: 128 × 64 dot LCD display, with 32 characters information
◎ Controller capacity:
A. a maximum capacity of 242 address coding points
B. external 64 fire show up; interconnection maximum 32 bed other type controller
C. 32 direct manual operation bus system control points
D. maximum configurable 10 more wire control points
◎ Wire:
A. controller and detector using polarity signal second bus connection
B. multiple wire control points and modules (LD-8302C) uses the promise of second-line connection
c.Controller and various coding module using four bus connection (polarity signal 2 bus, polarity dc24v)
D. controller and fire show up with four bus connection (with polar communications second bus, polarity dc24v)
E. and color CRT system connected via RS-232 standard interfaces, maximum length should not exceed 15m connector
◎ Using environment: temperature: 0 ° c ~ + 40 ° c relative humidity ≤ 95%, no condensation
¡Ò main power for power: AC 220V, sealed lead battery DC12V 10Ah be electro
◎ Power consumption ≤ 30W
◎ Dimensions: 400mm×560mm×178mm
(Ii) fire detectors
● JTY-GD-G3 type intelligent photoelectric smoke detector
JTY-GD-G3 intelligent photoelectric smoke detector with dedicated control chips and digital bus communication technology, with high reliability and ease of alarm installation. Can bus, annular or two ways mixed topology and automatic fire alarm controller connected to improve system maintainability.
This detector sensor part adopts backscatter maze structure that overcomes photoelectric smoke detector is not sensitive to smoke; the defect detector temperature compensation device settings, on the one hand the temperature drift correction devices, on the other hand on fire temperature variations can also provide a certain function of signal compensation and greatly improves the reliability of the alert.
This detector application intelligent fire algorithm, pass A/D conversion acquisition environment data, and data processing, to determine the current state of the environment. When the ambient temperature, dust, humidity and other conditions change, the probes can be automatically adjusted and compensation, increased reliability, reducing false positives.
Detector equipped with sensitivity adjustment function, sensitivity adjustment via host can also be achieved through the encoder. Sensitivity adjustment is determined according to need, such as daylight/night sensitivity adjustment, according to the scene environment conditions of sensitivity adjustment, etc.
Detectors can also be set in advance warning line, on particularly important occasions provide early pre warning function. When the environment parameters are detected by the probe reaches predefined alert line, the corresponding information to the controller, tips on duty personnel in the field, confirm that the fire.
Detector self-diagnosis function, the device is damaged, the labyrinth can be contaminated, such as self-censorship, and the controller issued a fault alarm signal. When the detector maze reached a certain dust accumulation, probe will alarm detector dust. Detector fault is divided into two levels of dust, the level is pre crash, when the dust accumulation has reached a high level, but will still be able to issue a fire scene detection, fire signal; the other level is down, even if compensation cannot be reliable alarm.
Detector equipped with traffic monitoring, detection and host communication situation. When found after the failure of communication with the controller, the detector automatically transferred to independent work mode. In independent mode, the detector according to predetermined algorithm on the monitoring of environmental conditions, when there is a fire environment, the probe will light up alarm lamp, indicate a fire. Detector in independent mode, still always detect communication signals, such as address recovery, the probe will pass the information main control system.
Detector able to record the duration of the collection of environmental data, and save the last time the alarm data. Detectors and controllers using digital bus communication, according to the command requires that the controller of the data are transmitted to the controller and graphics monitor your computer for display. Application, the system can also be set to host the detector alarm mode, the detector sensor function that fires the judgment by the host controller.
Detector design takes full account of the characteristics of the waterproofing. The entire probe into the cradle and the detection of the first two parts, the cradle only fixed pin terminals, not including other circuits. Detector, with sealed bottom side with overflow hole; terminal block design with waterproof jacket protection, ensure that there is water or water seepage of the spill, the detector can work properly. In addition, each detector in Circuit Board adopts the waterproofing process, the surface of a waterproof glue, guarantee the performance of moisture inside the detector. The detector's patented, Patent No.: ZL99311724.4.
The main technical indicators are as follows:
◎ Operating voltage: 24V bus
◎ Monitor current ≤ 0.8mA
◎ Alarm current ≤ 2.0mA
◎ Alarm acknowledgement lamp: Red flashes when the inspection, the alert always lit
◎ Using environment: temperature:-10 ℃ ~ + 50 ° c relative humidity ≤ 95%, no condensation
◎ Encoding: decimal electronic coding
◎ Dimensions: diameter: 100mm, high: 42mm (without base)
● JTW-ZCD-G3N type intelligent electronic differential fixed temperature heat detector
Smart electronic differential fixed temperature heat detector using high-quality electronic temperature sensors as well as a dedicated control chips and digital bus communication technology, stable performance, reliable. Probes according to application environment can be individually set to differential temperature or fixed temperature detector, and you can set the sensitivity of the differential temperature detector and a fixed temperature detector of alarm temperature to apply different places for the application.
Detectors can bus, annular or two ways mixed cabling and automatic fire alarm controller connected wiring flexibility, ease of installation.
Detector design takes full account of the characteristics of the waterproofing. The entire probe into the cradle and the detection of the first two parts, the cradle only fixed pin terminals, not including other circuits. Detector, with sealed bottom side with overflow hole; terminal block design with waterproof jacket protection, ensure that there is water or water seepage of the spill, the detector can work properly. This probe can be carried out through the handheld electronic coding encoder and performance checks, has good resistance to dust and moisture.
This detector is a patented product, patent number ZL99311722.8.BR > the main technical indicators are as follows:
◎ Operating voltage: 24V bus
◎ Monitor current ≤ 0.8mA
◎ Alarm current ≤ 2.0mA
◎ Alarm acknowledgement lamp: Red flashes when the inspection, the alert always lit
◎ Fixed temperature sensitivity level: fixed temperature sensitivity level 1: alarm setting temperature of 58 degrees centigrade; fixed temperature sensitivity level 2: alarm setting temperature 66 degrees centigrade; fixed temperature sensitivity level 3: alarm setting temperature 72 ° c.
◎ Using environment: temperature:-10 ℃ ~ + 50 ° c relative humidity ≤ 95%, no condensation
◎ Encoding: decimal electronic coding
◎ Dimensions: diameter: 100mm, high: 45mm (without base)
● JTY-GF-GST104-non-coding photoelectric smoke detector
With a new type of scattering technique and imports of optoelectronic devices and improves the reliability of the sensor, the stability and consistency, and a unique maze design, pest control, dust-proof, resistant to external light interference. Product novel structure, appearance, performance stable reliable, strong resistance to moisture, and has a good resistance to chemical corrosion. This detector alarm mode for the current type, with LD-8319 coding repeaters, LD-8320 active Terminal, you can access the company's production of various types of fire alarm controller, complete the detector signal processing.
The main technical indicators are as follows:
◎ Operating voltage: DC12V ~ DC28V
◎ Monitor current ≤ 60 μ A
◎ Alarm current: 10mA ~ 30mA
◎ Alarm acknowledgement, alarm lamp: Red often lit
◎ Using environment: temperature:-10 ℃ ~ + 50 ° c relative humidity ≤ 95%, no condensation
◎ Dimensions: diameter: 100mm, high: 42mm (without base)
● JTWB-ZCD-G1 (A) non-encoded electronic differential fixed temperature heat detector
JTWB-ZCD-G1 (A) non-encoded electronic differential fixed temperature heat detector is the use of temperature-sensitive components of sensitivity to detect the temperature, the built-in MCU, curing the high reliable fire judgment proceedings and with the special craft processing, stable and reliable, and has good resistance to chemical corrosion. This detector alarm mode for the current type, with LD-8319 coding repeaters, LD-8320 active Terminal used to access the company's production of various types of fire alarm controller, complete the detector signal processing.
The main technical indicators are as follows:
◎ Operating voltage: DC12V ~ DC28V
◎ Monitor current ≤ 60 μ A
◎ Alarm current: 10mA ~ 30mA
◎ Alarm acknowledgement, alarm lamp: Red often lit
◎ Using environment: temperature:-10 ℃ ~ + 50 ° c relative humidity ≤ 95%, no condensation
◎ Dimensions: diameter: 100mm, high: 45mm (without base)
● BT-KVA001 coding combustible roof home
BT-KVA001, BR-KVA001, BT-VA001, BR-VA001 coding combustible roof household use semiconductor gas sensor, stable, simple installation, this type of alarm using DC24V centralized power supply, and the various fire alarm controller coordinated application. For your home, hotel, apartment and other places where flammable gases exist for security monitoring. BT-KVA001, BR-KVA001 two products provide for the control of ventilation equipment for passive normally open contact and control of the gas pipelines of the solenoid valve is the contacts of the source. BT-VA001, BR-VA001 two products only provide control of the gas pipelines of the solenoid valve is the contacts of the source. BT-KVA001, BT-VA001 applies to detect natural gas, BR-KVA001, BR-VA001 applies to probe manufactured gas.
The main technical indicators are as follows:
◎ Detection components: the natural diffusion-type semiconductors
¡Ö power supply voltage: DC16V ~ DC30V
◎ Working current: monitoring current ≤ 80mA alarm current ≤ 100mA
◎ Alarm concentration: natural gas 5500ppm gas 1200ppm (H2)
◎ Warm-up time: 5 minutes
◎ Alarm: red LED flashes, accompanied by intermittent beeps
◎ Output contact:
Passive normally open contacts, capacity: 220V/3A,-only BT-KVA001, BR-KVA001
Active contacts, 0V ~ 12V one-way DC pulsed electromagnetic valve, drive capability: 2200 μ F/12 V capacitor discharge
◎ Using environment: temperature: 0 ° c ~ + 50 ° c relative humidity ≤ 95%, no condensation
◎ Dimensions: diameter: 137mm, high: 46mm (without base)
● BT-KVA002 coding combustible wall-mounted home
Encoding-mounted domestic combustible gas alarm using semiconductor gas sensor, stable, simple installation. This type of alarm using DC24V centralized power supply, and the Hudson Bay Company production of fire alarm controller to promise of second bus way to connect, and other types of fire detectors together to form a bus system, fire alarm system. Suitable for families, hotels, apartments and other places where flammable gases exist for security monitoring. There are two sound and light alarm status: general alarm and emergency alarm.
The main technical indicators are as follows:
◎ Detection components: the natural diffusion-type semiconductors
¡Ö power supply voltage: DC16V ~ DC30V
◎ Working current: monitoring current 80mA, alarm current 100mA
◎ Alarm concentration: gas (BT-Y002 series)
Level alarm: 10000ppm 7000ppm secondary alarm:
◎ Preheating timeRoom: 5 minutes
◎ Alarm: red LED flashes, accompanied by intermittent beeps. The general alarm, the red LED flashing frequency about 1Hz; emergency alert, red LED flashing frequency about 3Hz
◎ Output contact:
Passive normally open contacts, capacity: 220V/3A, only BT (R/Y)-KVA002 series
Active contacts, one-way 12V DC pulse electromagnetic valve, drive capability: 2200F/12V capacitor discharge
◎ Using environment: temperature: 0 ° c ~ + 50¡æ £ ¬2 relative humidity: 95%, no condensation
◎ Encoding: decimal electronic coding
◎ Dimensions: 176mm×80mm×45mm
● JTY-HS-G2-smart style infrared beam smoke detector
JTY-HS-G2-smart style infrared beam smoke detector built-in single-chip computer, have strong analytical judgment, by operation of the internal curing detectors may be auto-completion on the outside environment parameters change compensation and fire, failure of judgment and improves overall system detection accuracy of real-time and fire. The probes for use with the controller, you can fire alarm control system comprising, in particular, apply to the high-rise buildings, heritage protection construction facilities, Hall Museum, the warehouse group and tunnel project, where there is smoke in front of the fire formation of sites may use this product.
The probes debugging method is simple, debugging, use the fire light and fault lamp combination confirmation (on or off), and the controller of the ' fixed debug ' feature, you can continuously monitor the receiver light intensity trends for detector is debug, fix a non-intelligent infrared beam detectors for high-altitude on debugging difficult problems and job security.
The main technical indicators are as follows:
◎ Working voltage: transmitter: DC24V receiver: bus 24V
◎ Sink: monitor current ≤ 1.8mA, alarm current ≤ 2.5mA
Transmitter: monitor current ≤ 2.5mA (connected with 24V power supply, no polarity)
◎ Alarm acknowledgement lamp: Red fault led: yellow
◎ Using environment: temperature:-10 ℃ ~ + 50¡æ £ ¬2 relative humidity: 95%, no condensation
◎ Encoding: decimal electronic coding
◎ Dimensions: diameter: 100mm, high: 94mm (without base)
◎ Protected area:
This probe can be effective protection of a rectangular area, the largest protected area: 100m×14m
● JTW-LDB-100 type intelligent cable type heat detector
Smart cable type linear heat detector is JTW-LDB-100 type intelligent cable type linear heat detector coding interface, JTW-LDZ-100 type of Terminal and linear temperature sensor cable. This detector is the cable type heat detector, applicable to cable was in power and control cable fire early warning and control, power plants, steel mills, chemical plant, ancient buildings etc.
JTW-LDB-100 coding interface built-in single-chip computers that use electronic coding, line type heat detector access fire quotation system signal 2 bus. The first temperature sensor cable-end coding interface connection, end the connection with JTW-LDZ-100 type of Terminal. Each interface can connect two road temperature sensor cable, each occupying a code point.
Terminal for cable-linear heat detector private attachments, to the whole of the end of the temperature sensor cable without the need for access for fire alarm controller. Terminal with a temperature sensor cable fire test switch, easy to engineering simulation test pattern when debugging heat detector of alarm properties.
The main technical indicators are as follows:
◎ Operating voltage: 24V bus
◎ Monitor current ≤ 3mA
◎ Alarm current: 5mA
◎ Wire: interface and fire alarm controller with nonpolarized second bus connection terminal directly with linear temperature sensor cable connection
◎ Using environment: temperature:-10 ℃ ~ + 50¡æ £ ¬2 relative humidity: 95%, no condensation
◎ Dimensions: coding interface: Terminal: 120mm×80mm×40mm 162mm×200mm×80mm
● JTG-ZW-G1 type intelligent UV flame detector
UV flame detector by detecting material combustion produces ultraviolet to detect fires, apply to the fire occurred, easy to produce the open fire place, on the fires have strong flame or not smoldering stage places can be used this detector. The detector used in conjunction with other detectors, the timely discovery of fire, reduce losses.
UV flame detector sensor by use of imported components from UV-tube, with quick, reliable and resistant to dust, humidity and corrosive gases, etc.
The main technical indicators are as follows:
◎ Operating voltage: 24V bus
◎ Monitor current ≤ 2mA
◎ Alarm current: 10mA
◎ Wire: polarity signal 2 bus
◎ The detection angle ≤ 800
◎ Protection area: S = (h × t g α) 2 π (h: height from the ground, the detector α = 400)
◎ Alarm acknowledgement lamp: Red flashes when the inspection, the alert always lit
◎ Using environment: temperature:-20 ℃ ~ + 50 ° c relative humidity ≤ 95%, no condensation
◎ Dimensions: diameter: 100mm, high: 41mm (without base)
● JTF-GOM-GST601 type intelligent gas temperature composite probes
Compound detection technology is the internationally popular new multi-function high reliability of fire detection technology. JTF-GOM-GST601-flue gas temperature composite detector is my latest launch of a new detector, smoke sensors and semiconductor temperature sensors from process structure and circuit structure comprise of multiple complex detectors. It not only has intelligent photoelectric smoke detector performanceBut both fixed temperature, differential fixed temperature heat detector performance. It is precisely because of the smoke and heat of composite technology, makes this complex probes has overcome the normal forward scattering type photoelectric smoke detector smoke particles are not sensitive characteristics of smoke, to national standards test fire SH3 (polyurethane plastic fire) and SH4 (heptane fire) detection and alarm. At the same time that composite detector could also have significant alcohol burning temperature of fire detection and alarm, expanding the application of photoelectric smoke detector.
This detector is the promise of signal b bus system, you can access the Hudson Bay Company production of various types of fire alarm controller alarm bus. But these detectors with the Hudson Bay Company production of other probes are fully compatible, can be mixed on the same bus.
The main technical indicators are as follows:
◎ Operating voltage: 24V bus
◎ Monitor current ≤ 0.8mA
◎ Alarm current ≤ 2mA
◎ Alarm acknowledgement lamp: Red flashes when the inspection, the alert always bright, failure is off
◎ Fixed temperature alarm temperature: 90 ℃ (available through electronic encoder highest setting to 78 ° c)
◎ Using environment: temperature:-10 ℃ ~ + 50 ° c relative humidity ≤ 95%, no condensation
◎ Encoding: decimal electronic coding
◎ Dimensions: diameter: 100mm, high: 42mm (without base)
● JTGB-ZM-GST501/I/I-type flameproof UV flame detector
JTGB-ZM-GST501/I flameproof UV flame detector by detecting material combustion produces ultraviolet to detect fires, apply to the fire occurred, easy to produce the open fire place, and the other detectors, more timely detection of fire and minimize losses. JTGB-ZM-GST501/I flameproof UV flame detector for encoding flameproof products, explosion-proof performance conforms to GB3836.1-83 the explosive environment with explosion-proof electrical equipment-General requirements and GB3836.2-83 the explosive environment with explosion-proof electrical equipment flameproof electrical equipment "d" standard requirements while meeting GB12791-91 points-UV flame detector technical requirements and test methods "in the various requirements.
This detector explosion-proof type is suitable for explosion-proof ExdIICT6 zone 1 and zone 2 places various explosion-proof, according to the scene environment. Sensor made of imported products with high sensitivity, long life, reliable, etc. The detector used electronic encoding, available through our electronic encoder for encoding, encoding in the range between 1-242.
The main technical parameters are as follows:
◎ Operating voltage: 24V bus
◎ Monitor current ≤ 2mA, alarm current: 10mA
◎ Wire:-polarity and two-wire
◎ The detection angle ≤ 80
◎ Protection area: S (h * tg) 2 (h: detector is apart from the ground level, 40)
◎ Explosion-proof mark: ExdIICT6
◎ Using environment: temperature:-20 ℃ ~ + 40 ° c relative humidity ≤ 95%, no condensation
(3) alarm button
● J-SAP-8401-manual fire alarm button
J-SAP-8401 type intelligent coding manual alarm button design using innovative shape structure, recoverable characteristics, very suitable for application. Manual alarm button installed in public places, when artificial confirmed fire press the button on the plexiglass plate to the controller issued a fire alarm signal controller receives the alarm signal, displays the alarm button number or location and a beep sound. Manual alarm button directly on the receiving controller bus.
J-SAP-8401 type intelligent coding manual alarm button has the following characteristics:
(1) Manual alarm button uses the promise of signal b bus, its address coding by handheld electronic encoder in 1 ~ 242 between arbitrary.
(2) Manual alarm button uses the pluggable type structure design, button presses on the plexiglass film press reset after special tools available.
(3) press the alarm button glass, can be used by buttons provide rated DC60V/100mA passive output contact signal, can directly control the other external devices.
Manual alarm button uses the entire seal design, seams designed the gasket, with waterproof function. In addition, the Board adopts the waterproofing process, the surface of a waterproof plastic to protect the hand button on the inside of the moisture-proof performance.
The main technical indicators are as follows:
◎ Operating voltage: 24V bus
◎ Monitor current ≤ 0.8mA
◎ Action current ≤ 2mA
◎ Wire: and controller-polarity signal second bus connection
◎ Using environment: temperature:-10 ℃ ~ + 50¡æ £ ¬2 relative humidity: 95%, no condensation
◎ Dimensions: 90mm×122mm×48.5mm
● J-SAP-8402-manual fire alarm button (with the phone jack)
J-SAP-8402 intelligent coding manual alarm button (with the phone jack) design using innovative shape structure, recoverable characteristics, very suitable for application.
This manual alarm button electronic encoding, once confirmation beep, immediately signals to the controller, warning prompt. Manual alarm button located on the phone jack, when handheld phone after inserting the call should be made with the control center.
Manual alarm button uses the entire seal design, seams designed the gasket, with waterproof function. In addition, the Board adopts the waterproofing process, the surface of a waterproof plastic to protect the hand button on the inside of the moisture-proof performance.
The main technical indicators are as follows:
◎ Operating voltage: 24V bus
◎ Monitor current ≤ 0.8mA
◎ Action current ≤ 2mA
◎ Wire: and controller uses the promise of signal b bus connection and bus system coding telephone jack connection using four-wire, and TS-Z02 multiple wire telephone hosts connections using phone II bus
◎ Using environment: temperature:-10 ℃ ~ + 50¡æ £ ¬2 relative humidity: 95%, no condensation
◎ Dimensions: 90mm×122mm×48.5mm
● LD-8403 type intelligent encoding fire hydrant alarm button
LD-8403 type intelligent fire hydrant alarm button for encoding type, you can directly access controller bus, representing an address encoding.
Button face a plexiglass plate, when enabled, fire hydrant, can be directly pressed glass, where the red light on the button, indicating that the control room to the fire alarm information was issued, the controller confirmed the fire pump has started running, to issue a fire hydrant alarm button command signal light pump operation indicator. Fire hydrant alarm button of pump operation led to the controller, also attracted by the pump control box direct pump running switch signal lights, according to the specific design requirements.
Alarm button uses the pluggable type structure design, button presses on the plexiglass film press reset after special tools available.
Alarm button electronic coding that uses the entire seal design, seams designed the gasket, with waterproof function. In addition, the Board adopts the waterproofing process, the surface of a waterproof glue, guarantee the performance of moisture inside the button.
The main technical indicators are as follows:
◎ Operating voltage: 24V bus
◎ Monitor current ≤ 0.8mA
◎ Alarm current ≤ 2mA
◎ Wire: fire hydrant alarm button signal with the controller, the second bus connections if you need to achieve direct cycle pump control and pump control box action lit pump running lights, fire hydrant and alarm buttons and pump control box are three bus connection
◎ Action led:
Red: the alarm button is pressed the lights green: the fire pump starts this lights
◎ Actions-contact: passive normally open contacts, with a capacity of DC60V, 0.1A, can be used to direct cycle pump control
◎ Using environment: temperature:-10 ℃ ~ + 50¡æ £ ¬2 relative humidity: 95%, no condensation
◎ Dimensions: 90mm×122mm×48.5mm
● LD-8404 type intelligent encoding fire hydrant alarm button
LD-8404 intelligent encoding button design fire hydrant alarm has started and answer indicates that the command State can be clearly displayed and the operation of the pump. The fire hydrant Manual alarm button has direct cycle pump function, when connected to the controller fails, you can start by it directly connected to fire hydrants pump, monitoring the operation of the fire pump. Fire hydrant pump action, feedback signal will light the fire hydrant Manual alarm button answer led.
This button is encoding type, you can directly access the Hudson Bay Company production of various fire alarm controller or linkage controller, encoded using electronic encoding, encoded in the range between 1-242, available through our BMQ-1 type electronic encoder setting in the field. Button has two LEDs, Red LEDs for the fire indicates that when the button is pressed; the Green led is lit to action indicator, indicator is lighting if the scene after the device action. This button has DC24V active output and on-site equipment, the use of passive answer input three-wire system and the device is connected, you can finish the equipment start-up and monitoring. This way you can independently of the controller, cut off the alarm signal bus, can still be manually by pressing start fire pumps and light alarm and pump action led.
Alarm button uses the entire seal design, seams designed the gasket, with waterproof function. In addition, the Board adopts the waterproofing process, the surface of a waterproof glue, guarantee the performance of moisture inside the button.
The main technical indicators are as follows:
◎ Operating voltage: 24V bus
◎ Monitor current ≤ 0.5mA
◎ Alarm current: 5mA
◎ Wire: and alarm controller uses two bus connection and power supply connection with two lines, and fire pump adopts three-wire system connection (an active output DC24V, a answer line-in, a root of public land)
◎ Action led:
Red: the alarm button is pressed the lights green: on-site equipment action after the lights
◎ Actions-contact: passive normally open contacts, with a capacity of DC60V, 0.1A, can be used to direct cycle pump control
◎ Using environment: temperature:-10 ℃ ~ + 50¡æ £ ¬2 relative humidity: 95%, no condensation
◎ Dimensions: 90mm×122mm×48.5mm
(4) onsite module and interface devices
● LD-8300-monitoring module
LD-8300-Smart encoding for single-input module can be the scene of various proactive equipment such as flow meter, pressure switch, break glass button, access to the fire alarm signal of the controller, the device on the bus movements, output switch signal will be fed into the fire alarm controller LD-8300, generate alerts, and through the controller coordinated action in other equipment. This module uses the electronic coding that is available through the encoder achieve its address set. This module the desired signal to off¡á1 switching signal, the signal as soon as the switch, the switch signal LD-8300 through signal bus into the controller, the controller generates an alert and displays the address of the device that the action, while enabling module actions led is lit. When the module itself fails, the controller will also be on the alert and the module number displayed. This module size is very small, the installation is very easy.
The module uses the entire seal design, seams designed the gasket, with waterproof function. In addition, the Board adopts the waterproofing process, painted with water-proof rubber, guaranteed performance against moisture inside the module.
The main technical indicators are as follows:
◎ Operating voltage: 24V bus
◎ Monitor current ≤ 0.8mA
◎ Action current ≤ 2mA
◎ Wire: and controller signals second bus connection
◎ Using environment: temperature:-10 ℃ ~ + 50¡æ £ ¬2 relative humidity: 95%, no condensationBR > ◎ dimensions: 120mm×80mm×39mm
● LD-8301-Smart encoding for single-input/single-output module
LD-8301-Smart encoding for single-input/single output modules for various various scene once the action and the action returned passive equipment such as exhaust vents, air, fire dampers, access to the controller of signal buses. Controller based on the linkage between advance input to satisfy the launch condition of device startup command, the module receives the start command, pass the corresponding start unit start joint fire equipment. Linkage device actions, the device always output contact closure, the module will convert this switch signal alarm signal, by bus to the controller issued a device action answer signal, the controller will display the number of actions, and the device emits a beep sound. The module has a pair, one pair of normal close output contact and enter a normally open contact (available through electronic encoder changes to normally closed type), output contact capacity is 5A, DC24V. Module with actions led, flashing during the normal state; when the controller issued starting signal, the led is lit. Module input signal should be passive signal, when the field equipment without answer signal generation, accessible via electronic encoder set to auto-answer mode to confirm the module actions. When the module itself fails, the controller will also be on the alert and the module number displayed. The encoding for e-mail encoding, encoding simple and fast.
The module uses the entire seal design, seams designed the gasket, with waterproof function. In addition, the Board adopts the waterproofing process, painted with water-proof rubber, guaranteed performance against moisture inside the module.
The main technical indicators are as follows:
◎ Operating voltage: 24V bus
◎ Monitor current ≤ 1mA
◎ Action current ≤ 5mA
◎ Wire: and controller uses the promise of signal b bus connection and power supply with nonpolarized DC24V power second bus connection
◎ Using environment: temperature:-10 ℃ ~ + 50¡æ £ ¬2 relative humidity: 95%, no condensation
◎ Dimensions: 80mm×120mm×39mm
● LD-8303 intelligent encoding two-input/dual output module
LD-8303 intelligent encoding two-input/dual output modules can be used to complete the double action device control. Mainly used in the second step in reducing fire shutter position control and fan, water pump and stopping control. The module can also be used as two separate LD-8301 smart single-input/single output modules. LD-8303 intelligent encoding two-input/dual output module with two encoded addresses that are independent of each other, which can be received from the controller of the second order of different actions, with a second different control output and confirm the second answer different input signal. This module is always required to signal switch signal, once the switch signal actions, this switch signal LD-8303 by bus into the controller, the controller generates an alert and displays the address of the device that the action, meet the linkage relationship can make the module actions. When the module itself fails, the controller will also be on the alert and the module number displayed. This module has two normally open, normally closed contact that capacity is 5A, DC24V, active output DC24V 1A, can be output. LD-8303 module encoding for e-mail encoding, that encoding modes simple and fast.
The module uses the entire seal design, seams designed the gasket, with waterproof function. In addition, the Board adopts the waterproofing process, painted with water-proof rubber, guaranteed performance against moisture inside the module.
The main technical indicators are as follows:
◎ Bus operating voltage: 24V bus
◎ Bus monitor current ≤ 1mA
◎ Bus current ≤ 8mA
◎ Wire: and controller uses the promise of signal b bus connection and power supply with nonpolarized DC24V power second bus connection
◎ Using environment: temperature:-12 ° c to + 50 ° c relative humidity ≤ 95%, no condensation
◎ Dimensions: 80mm×120mm×39mm
● LD-8304 coding fire telephone module
LD-8304 module is a direct encoding module, and the fire alarm controller bus connection and need to be connected to the power bus DC24V. In addition, in order to achieve the delivery of telephone voice signal, you need to access the fire phone bus. LD-8304-module has a telephone jack, you can direct telephone extension for bus system.
And the second bus controller for signal and power second bus connections; and bus system fire phone call the host bus connections; if you want access phone socket, instead of using four-wire connection.
● LD-8305 coding fire radio switch module
LD-8305 coding fire radio switch module designed for bus system fire broadcasting system remain within the various fire compartment fire radio broadcast and switching between control. The module is equipped with auto-answer feature, when the module actions will generate an alarm signal is fed into the controller generates alerts indicating that the switch was successful.
The main technical indicators are as follows:
◎ Bus voltage: DC24V bus
◎ Bus monitor current ≤ 1mA
◎ Bus current ≤ 7mA
◎ Wire:
A. controller signals second bus and power second bus connection
B. can access two normal broadcast cable and two fire broadcasting line
◎ Using environment: temperature:-10 ℃ ~ + 50¡æ £ ¬2 relative humidity: 95%, no condensation
◎ Dimensions: 80mm×120mm×39mm
● LD-8311-bus relay fiber interface
Bus relay fiber interface by the receiver module, transmitter module and fibre. Applies to the detection area can not be used cable and radio waves transmit signals, but also for the detector and the module and the distance is greater than the fire controller 1.5 km. The bus relay fiber interface using optical fiber for signal transmission medium, with the transmission frequency bandwidth, insulationBe good, anti-radiation, strong anti-interference ability, light weight, corrosion resistance and other advantages. Particularly applicable to nuclear radiation, EHV power systems and strong electromagnetic interference, minefield, inflammable, explosive and highly corrosive environments, etc.
The main technical indicators are as follows:
◎ Receiver module voltage: 24V bus
Receiver module operating current: 15mA to monitor current ≤, alarm current ≤ 20mA
Transmitter module voltage: DC24V
Transmitter module working current: 300mA of current ≤ monitoring, alarm current: 500mA
◎ Single-mode fiber optic specifications: (9/125 μ m) or die (50/125 μ m, 62.5/125 μ m) fiber optional
◎ Transmission distance ≤ 30km
◎ Using environment: temperature:-10 ℃ ~ + 50 ° c relative humidity ≤ 95%, no condensation
◎ Dimensions: receiver module: 126mm×65mm×30mm; transmitter module: 175mm×75mm×30mm
● LD-8313-bus isolator
When the bus fails, the failure of bus parts and isolate an entire system to ensure that the system of the normal work of the other part, to determine the failure of bus parts. When the failed part of the bus after repair, bus isolators can resume work, will be separated out part into the system, maintenance is simple. LD-8313-bus isolator based on actual number set by the next detector with load capacity of their own, bus isolator with 170mA and 270mA two current, direct-line on the bus, using flexible.
The main technical indicators are as follows:
◎ Operating voltage: 24V bus
◎ Action current: 170mA (maximum access 50 coding equipment); 270mA (maximum access 100 encoding device)
◎ Quarantine actions confirm lamp: Red
◎ Using environment: temperature:-10 ℃ ~ + 50¡æ £ ¬2 relative humidity: 95%, no condensation
◎ Dimensions: 120mm×80mm×39mm
● LD-8319 coding repeaters
LD-8319 coding Repeater is a code module that is used to connect non-encoding detector, occupies only one code point, when the access code relays output circuit of any field device alarm, the alarm relays information to the alarm controller, controller generate alarm signals and display the address of a Repeater. Repeaters can be with the company's production of JTFB-GOF-GST601 noncoding flue gas temperature composite detector, JTY-GF-GST104 noncoding photoelectric smoke detector and JTWB-ZCD-G1 (A) non-encoded electronic differential fixed temperature heat detector, etc. Repeater with output circuit breaker test function, output circuit terminal connection active Terminal LD-8320, when output circuit breaker, coding repeaters will fault information to alert the controller, the controller displays the encoding of the repeaters; when the output circuit with on-site equipment is removed, the encoding will report a failure but a Repeater does not affect the other field devices work correctly. A Repeater can bring many non-encoding detector, you can also mix multiple detectors, but mix the quantity not exceeding 15 only.
Repeaters using four-wire system, the controller needs two alarm signal bus (polarity) and two dc24v (polarity), encoding the relays output polarity with probes used a two-wire connection.
Repeater address coding using electronic encoding encoding range 1 ~ 240 set between, the Hudson Bay Company production of BMQ-1 type electronic encoder for scene changes.
LD-8319 coding repeaters and non-encoding detector series connection, the detector base should add diode 1N5819, and output circuit terminal must add LD-8320 active Terminal. A source terminal can be used when the detector base, that is, the source terminal can be installed non-encoding detector. When a source Terminal is not used as a detector base, should be loaded on the cover. The engineering equipment configuration in order to reduce costs, using Active terminal when the detector base used in active Terminal directly installed non-encoding detector installation mode that reduces the number of the detector base.
The main technical indicators are as follows:
◎ Operating voltage: 24V voltage bus: bus, power supply voltage: DC24V
◎ Monitor current ≤ 0.5mA
◎ Alarm current: 5mA
◎ Wire: and controller uses the promise of signal b bus connection and power supply cord with promise of two-wire connection, and non-encoding detector using polarized two-wire connection
◎ Using environment: temperature:-10 ℃ ~ + 50¡æ £ ¬2 relative humidity: 95%, no condensation
◎ Dimensions: 120mm×80mm×40mm
● LD-8320 active Terminal
In non-coding automatic fire alarm system, the traditional way is through the circuit terminal connection a resistance to maintain the system's normal work, once the entire matching undue alarm system is not functioning, or even produce a false alarm. LD-8320 active Terminal and supporting the use of LD-8319 coding repeaters to replace terminal resistor, when the alarm system output circuit with on-site equipment is removed, the Repeater to LD-8319 coding controllers report fails, but does not affect the other field devices work correctly. Effectively solved the above problem, greatly improving non-coded alarm system reliability.
The main technical indicators are as follows:
◎ Working voltage: DC15V ~ DC28V
◎ Nominal voltage: DC24V
◎ Equivalent resistance: 4.7 k Ω
◎ Using environment: temperature:-10 ℃ ~ + 50¡æ £ ¬2 relative humidity: 95%, no condensation
◎ Dimensions: diameter: 103mm, high: 38mm
(5) fire show up
● ZF-101 fire show up
ZF-101 fire show up is a single-chip design and development can be installed on the floor or independent zones digital fire alarm display device. By bus and fire alarm controller, handling and display controller transfer over the data. When building a fire, the fire control centre of the fire alarm controller generate alarm, alarm signal is transmitted to the fire area fire shows up. Displays the disc will result in a fire alarm detectors numbers and related information is displayed, and produces sound and light alarm signal, to notify the fire zone. Fire show up with 8-bit alarming information display window, you can set alarm detector code number shown to meet a wide range of alarm display requirements. When using a single alarm controller while monitoring several floors or fire partitions, each partition set floors or fire fire shows up in place of the area alarm controller.
The main technical indicators are as follows:
◎ Display range: display range: 000000 00 ~ 99 any alarm in 999999 coding points
◎ Shows capacity: up to 50 of alarm information
◎ Wire: and fire alarm controller using a polarity second bus connections to two DC24V power supply cable (no polarity)
◎ Using environment: temperature: 0 ° c ~ + 40 ° c humidity: ≤ 95%, no condensation
◎ Power: DC16.8V ~ DC26.4V power centralized power supply
¡Ò saving state power consumption ≤ 1W, maximum power consumption ≤ 2W
◎ Dimensions: 230mm×142mm×70.5mm
● ZF-500 type Chinese character LCD display tray fire
ZF-500 fire displays disc is single-chip design and development of kanji-fire show up to show the fire detectors part number and character information and at the same time issued a sound and light alarm signal, the display is clear and intuitive, easy to confirm. By bus and fire alarm controller, handling and display controller transfer over the data. When an alarm while monitoring several floors or fire partitions, each partition set floors or fire fire shows up in place of the area alarm controller.
The main technical indicators are as follows:
◎ Display range: each screen displays 4 alarm information, subsequent alarm information can cycle through the
◎ Shows capacity: up to 126 alarm information
◎ Wire: and fire alarm controller using a polarity second bus connections to two DC24V power supply cable (no polarity)
◎ Using environment: temperature: 0 ° c ~ + 40 ° c humidity: ≤ 95%, no condensation
◎ Power: DC16.8V ~ DC26.4V power centralized power supply
¡Ò saving state power consumption ≤ 2W, 3W max power consumption ≤
◎ Dimensions: 230mm×142mm×70.5mm
● ZF-GST8903-graphical fire show up
Fire show up is ZF-GST8903 a floor of fire alarm display device. When the fire control centre of the host receives a building after fire, alarm, the alarm signal is transmitted to the fire area fire shows up, fire show disk will produce an alert detector location displayed and a beep sound to notify the fire zone.
This shows up for non-standard products, according to the project actual requirements and under fire shows up the displayed alarm zone layout customization.
The main technical indicators are as follows:
◎ Display range: 1 ~ 64 encoding.
◎ Shows capacity: up to 64 alarm message.
◎ Wire: and fire alarm controller using a polarity second bus connections to two DC24V power supply cable (no polarity).
◎ Using environment: temperature: 0 ° c ~ + 40 ° c humidity: ¡ü95% (40 ° c, 2 ° c)
¡Ö power supply: DC24V power centralized power supply, power dissipation ≤ 1W
◎ Dimensions: 345mm×235mm×70mm
(6) power
● GST-DY-100-type power supply box
GST-DY-100-power box is a DC24V bulk power output equipment, fire alarm control system that can be used as a coordinated control system of power, as linkage control module and charged device power supply. Power supply unit to the AC 220V as main power, while the built-in DC24V/7Ah sealed lead batteries as backup power supply, switching power supply voltage circuits and maintain electrical floating charge, with output over-current protection, and standby power switch and the perfect preparation of electric power by automatically charging and over-discharge protection. At the same time, the intelligent power supply unit can be kept on the main, electrical and power output status monitoring, master, power failure, fault output, but also has an output voltage, output current display feature to visually observe power box working state.
The main technical indicators are as follows:
◎ Rated output capacity: DC24V, 4A
◎ Using environment: temperature: 0 ° c ~ + 40 ° c relative humidity ≤ 95%, no condensation
¡Ò main power for power: AC 220V, built-in DC24V 7Ah sealed lead batteries be electro
◎ Dimensions: 310mm×400mm×115mm
● GST-DY-200-smart power box
GST-DY-200-smart power box is a DC24V bulk power output equipment, fire alarm control system that can be used as a coordinated control system of power, as linkage control module and charged device power supply. Power supply unit to the AC 220V as main power, while the built-in DC24V/24Ah sealed lead batteries as backup power supply, switching power supply voltage circuits and maintain electrical floating charge, with output over-current protection, and standby power switch and perfect automatic charging byAnd maintain power over discharge protection. At the same time, the intelligent power supply unit can be kept on the main, electrical and power output status monitoring. When the input voltage is greater than or less than 260V 160V times main power failure; when preparing electrical battery damaged or undervoltage electrical fault when filing; when the output voltage is greater than the 28V or output current greater than 8A times output fault. The power box also has a main electrical voltage, output voltage, output current display feature to visually observe power box working state.
The main technical indicators are as follows:
◎ Rated output capacity: DC24V, 6A
◎ Using environment: temperature: 0 ° c ~ + 40 ° c relative humidity ≤ 95%, no condensation
¡Ò main power for power: AC 220V, built-in DC24V 24Ah sealed lead batteries be electro
◎ Dimensions: 500mm×440mm×170mm
● GST-LD-D02-intelligent power-up
GST-LD-D02-intelligent power disk circuit by AC-DC conversion, standby power float control circuit and power control circuit is composed of three parts, specifically for the entire fire control system power supply.
GST-LD-D02-intelligent power up to AC 220V as main power, while the external battery DC24V/24Ah as preparation. Standby power normally accept main power charging, when the site AC power failure, the standby power supply automatically import external supply. Intelligent power supply tray can be on the main electrical faults and alarm output failure, when the input voltage is greater than or less than 160V 260V, reported main power failure; when the output voltage is greater than the 28V or output current greater than 8A, report output. At the same time it also has a battery overcharge and over discharge protection. Power monitor parts for indicating that what is currently being used by all the way to the power supply, AC input voltage and output voltage values, as well as various fault and status display. In a tank fire alarm controller (linkage) as the control core systems, the power-up as a coordinated control system power.
The main technical indicators are as follows:
◎ Output capacity: DC24V, 6A
◎ Using environment: temperature: 0 ° c ~ + 40 ° c humidity: ≤ 95%, no condensation
¡Ò main power for power: AC 220V, built-in DC24V 24Ah sealed lead batteries be electro
(VII) fire broadcasting system
• Bus system fire emergency broadcasting system
Fire emergency broadcasting system belongs to the fire alarm control system supporting the use of equipment, through this system you can achieve communication building fire, command related layer evacuation capabilities throughout the fire control system plays an extremely important role.
Bus system fire emergency broadcasting system by the Hudson Bay Company production of fire control centre of the broadcast equipment, with the use of the bus system for fire alarm controller, LD-8305 fire radio module and playback devices. The fire control centre of the broadcast equipment including radio power amplifier, CD recording disc GST-CD type and GST-KZ-deck recording disk, you can set in the Cabinet. Live broadcast using roof and wall-mounted speakers. Use fire radio switch module LD-8305, scene playback device on the bus access controllers, sent by the radio device to the audio broadcast signals, but also through LD-8305 module passive normally open contact (fire broadcasting) and normally closed contact (normal broadcast) added to the playback device, a radio range may be a LD-8305 module to control. The module is equipped with auto-answer feature, when the module actions will generate an alarm signal is fed into the controller generates alerts indicating that normal broadcast and fire broadcasting switch successfully.
Fire emergency broadcasting system playback device can be private or share with the public broadcasting system; when combined with the public broadcasting system, the fire control centre must be fire evacuation level for the speakers and to public broadcasting amplifiers force fire emergency broadcast status while in the fire control centre monitors fire emergency radio amplifiers working state.
Fire broadcasting equipment together with other devices can also be individually assembled in fire control cabinets, equipment power unity by fire control system of power supply.
«More wire fire emergency broadcasting system
Fire emergency broadcasting system belongs to the fire alarm control system supporting the use of equipment, through this system you can achieve communication building fire, command related layer evacuation capabilities throughout the fire control system plays an extremely important role.
More wire fire emergency broadcasting system by the Hudson Bay Company production of fire control centre of the broadcast equipment, fire alarm controller, LD-GBFP-100 multiple wire broadcast distribution and live broadcast speaker. The fire control centre of the broadcast equipment including radio power amplifier, CD recording disc GST-CD type and GST-KZ-deck recording disk, you can set in the Cabinet. Live broadcast using roof and wall-mounted speakers. More wire fire broadcasting system's output of broadcasting channels by broadcasting Division to design, each broadcasting a second root partition independent broadcasting channels and live playback devices are connected, the broadcast Division switching control by the fire control centre dedicated multi wire fire broadcast distribution (LD-GBFP-100 type). With this switch, you can complete manually on the broadcasting Division for normal or fire radio switch.
Fire emergency broadcasting system playback device can be private or share with the public broadcasting system; when combined with the public broadcasting system, the fire control centre must be fire evacuation level for the speakers and to public broadcasting amplifiers force fire emergency broadcast status while in the fire control centre monitors fire emergency radio amplifiers working state.
Fire broadcasting equipment together with other devices can also be individually assembled in fire control cabinets, equipment power unity by fire control system of power supply.
(8) fire telephone system
• Bus system fire telephone system
Fire telephone system is a dedicated communication systems for fire, this system can quickly achieve on fireDisaster manual confirmation, and may hold the fire site and carry out other necessary communications, to direct the fire suppression and recovery work. Telephone system host installation in the control center, the use of embedded installed in the alarm control stringed Cabinet.
The complete bus system fire telephone system consists of a set of fire control centre GST-TS-Z01A-bus system fire phone host and fire alarm controller, on-site LD-8304 module and LD-8312-phone jack and TS-100A fire telephone extension. The system has a design flexible, easy to use and so on.
GST-TS-Z01A-host with recording function, using digital voice memory chips up to record a 30-minute call to fire accident investigation.
LD-8304 module is a direct encoding module, and the fire alarm controller bus connection and need to be connected to the power bus DC24V. To achieve the delivery of telephone voice signal, you need to access the fire phone bus. LD-8304-module has a telephone jack, you can direct telephone extension for bus system.
LD-8312-phone jack and J-SAP-8402 type intelligent coding manual alarm button telephone jack parts are non-coding, direct bus connections with fire telephone constitute non-coded telephone jack, if-module connection with LD-8304, may constitute a coding style phone jack.
Fire telephone system telephone extension can call host without dialing, ringing when the host is the call until the host off-hook or extension to cancel the call; at the same time, the host may call any fixed extension (by fire alarm controller), the extension is ringing when the call until the extension off-hook or cancel the call of fire alarm controller; extension between host allows also can call; telephone jacks can be expanded. Pick a fixed telephone extension or extension plugged LD-8312-Jack and J-SAP-8402-Manual alarm button (including telephone socket) phone jacks are considered extensions caller host. The host calls fixed extension can fire alarm controller starts the appropriate LD-8304 modules allow extension ring. Host and extension, extensions and extension of the call, the call is completed by the host's own control without the need for other controllers.
«More wire fire telephone system
Fire telephone system is a dedicated communication systems for fire, this system can quickly achieve the fire of artificial confirmation, and may hold the fire site and carry out other necessary communications, to direct the fire suppression and recovery work. Telephone system host installation in the control center, the use of embedded installed in the alarm control stringed Cabinet.
Complete wire fire telephone system consists of a set of fire control centre TS-Z02A-multi wire fire phone host and fire alarm controller, LD-8312-phone jack and TS-200A stationary fire telephone extension and TS-200B hand-held fire telephone extension. The system has a design flexible, easy to use and so on.
More wire fire telephone system control core for multiple-line TS-Z02A-fire phone hosts. According to the actual demand, fire phone hosts capacity is not the same. Fire in a multiple-line telephone system, each Department TS-200A type fixed fire Ext. occupy all the way to fire phone hosts, separate two-wire and fire phone hosts connections. LD-8312-fire phone jack can be connected in parallel, parallel, or as many as you like, parallel telephone jack fire phone only occupies one of the host.
Fire telephone system telephone extension can call host without dialing, ringing when the host is the call until the host off-hook or extension to cancel the call; at the same time, the host may call any fixed extension (by fire alarm controller), the extension is ringing when the call until the extension off-hook or cancel the call of fire alarm controller; extension between host allows also can call; telephone jacks can be expanded. Pick a fixed telephone extension or extension plugged LD-8312-type jacks are considered extensions caller host.
More wire fire telephone system host and extension, extensions and extension of the call, the call is completed by the host's own control without the need for other controllers.
(9) gas extinguishing control
● LD-QKP06 type gas fire extinguishing Control Panel
LD-QKP06 gas extinguishing Control Panel is a project of the actual requirements of gas fire extinguishing control interface device, used to drive a gas fire extinguishing system of executive bodies, so as to constitute a complete gas fire control system. This control panel you can directly access fire alarm controller bus, and the company's production of linkage controller or fire alarm controller together with the completion of the gas cylinders, automatic control to control fire extinguishing gas spray.
The control panel can be independent of the linkage controller or fire alarm controller on the connected external device control. The fire alarm controller when an exception occurs, through on-site emergency start/stop-button or the gas fire extinguishing Control Panel on start and stop moving directly to the key realization on gas fire extinguishing equipment of control actions.
LD-QKP06 gas extinguishing Control Panel can be attached spraying led, emergency boot/shutdown action buttons, independent control linkage more wire devices. Extinguishing control panel with external line short circuit and open circuit check alarm function, and have an alternate number line output to ensure that the main gas fire extinguishing equipment maintenance or failure to use an alternate control output reached gas extinguishing purposes.
The main technical indicators are as follows:
◎ Capacity: maximum capacity of control 6 gas fire district (six control unit)
◎ 0s---45s adjustable delay time:
◎ Wire:
A. controller uses two bus connection (polarity signal second bus)
B. steel solenoid valve, pressure switch and spray led multiple wire 2-wire connection
C. emergency boot/shutdown dynamic buttons using multiple wire 3-wire connection
D. xiangqi with sound and light; adopts 2-wire connection
E. exterior with nonpolarized DC24V power
◎ Output: the output tray has 6 points, each group has two DC24V output (main and standby fire)
◎ Using environment: temperature: 0 ° c ~ + 40 ° c relative humidity ≤ 95%, no condensation
◎ Power: DC24V6V (for), you can connect with intelligent power-up or intelligent power box
◎ Monitor power consumption ≤ 10W
◎ Dimensions: 460mm270mm 105mm
● Gas extinguishing control card
Gas extinguishing control card by LD-KZC-200-gas fire extinguishing CPU control card and KZK-200-gas fire zone control card, designed and JB-QB-GST200-type fire alarm controller (linkage), constitute the set alarm linkage control, gas fire in one of the controller, used to drive a gas fire extinguishing system of executive bodies, so as to constitute a complete gas fire control system.
A LD-KZC-200-gas fire extinguishing CPU control card and a piece of KZK-200-gas fire zone control card, you can complete a gas fire extinguishing partition control; each additional gas fire partitions, you need to add 1 block KZK-200-gas fire extinguishing regional control card. JB-QB-GST200-type fire alarm controller (linkage) can control four gas fire partitions.
This control card with output line circuit breaker, short-circuit alarm function, these detection feature can maximize security control card itself and its connection with important device reliability.
The main technical indicators are as follows:
◎ Wire:
A. controller uses two bus connection (polarity signal second bus)
B. Control card and steel solenoid valve, pressure switch and spray indicator used second-line connection
C. Control card and start/stop and emergency action button adopts three-wire connection
D. xiangqi with sound and light; adopts 2-wire connection
E. exterior with nonpolarized DC24V power
◎ Gaseous fire extinguishing 0s---45s adjustable delay time:
◎ Using environment: temperature: 0 ° c ~ + 40 ° c relative humidity ≤ 95%, no condensation
¡Ö power supply: DC24V
◎ Monitor power consumption ≤ 2W (a gas fire district)
● LD-8317A-gas spray indicator
LD-8317A gas spray indicator is a gas fire extinguishing system of matching products, usually installed in a protected area of the entrance. When gas sprays, the controller will start gas spray led lights indicate that remind staff attention and take the appropriate measures.
Gas spray led to non-encoding type, you can directly access DC24V power.
The main technical indicators are as follows:
◎ Working voltage: DC20V ~ DC28V
◎ Normal operating voltage range: DC21.5V ~ DC26.5V
◎ 100mA current ≤
◎-Wire system: two-wire, and LD-QKP06 gas extinguishing Control Panel connections
◎ Using environment: temperature:-10 ℃ ~ + 50¡æ £ ¬2 relative humidity: 95%, no condensation
◎ Dimensions: 280mm46mm 110mm
● LD-8318A-emergency stop-button start/
Emergency stop button to reboot/control gas fire extinguishing system startup and stop moving, usually installed on the site. When the protected area in the event of a fire emergency, press the Start button, then the gas fire extinguishing Control Panel signals, gas fire extinguishing Control Panel after 30 seconds delay start gas sprays solenoid valve, if the field confirm that no fire occurred, immediately press the emergency button to stop moving, interrupt latency, emergency shut-off gas spray control signal. To avoid misoperation, start and stop moving button with glass cover for protection, when the fire first smash glass before you press the corresponding button after timely replacement glass.
This button is non-coding ways to start and stop the movement are not accounted for encoding.
The main technical indicators are as follows:
◎ Working voltage: DC24V
◎ Monitor current: 0mA
◎ Alarm current ≤ 20mA
◎ Always output contact: ratings 60VDC, 0.1A, contact resistance ≤ 0.1
◎ Wire: controller with gas fire three-wire connection
◎ Using environment: temperature:-10 ℃ ~ + 50 ° c relative humidity ≤ 95%, no condensation
◎ Dimensions: 90mm144mm60mm
(10) many wire linkage control device
● KZK-100-multiple wire control card
KZK-100-multiple wire control card is designed for the fire control system in important equipment: fire, smoke machine, blower, etc. implement reliable control. This control card for mould-plastic structure that can be used with all types of fire alarm controller, and according to practical engineering needs flexible configuration control points, composition dedicated multi wire control panel.
KZK-100-multiple wire control card is equipped with a manual output control and automatic linkage function, in manual mode, you can use the keys on the control card to complete the on-site equipment manual control; if you need to implement automatic control, you must set the control card access fire alarm controller signal bus, and the controller logic by on-site preparation of joint formula command control card external control equipment for automated linkage control.
Control Panel output terminal has a short circuit, open circuit detection and device status detection function, and have appropriate lighting, comply with the requirements of GB16806-1997.
The main technical indicators are as follows:
¡Ò control card capacity: each control card with 2-channel output, independent control of each channel can be a continuous or pulse device, take a bus address coding points
◎-Wire system: the control card and charged device connection, in order to ensure the connecting lines can be checked and prevent the exchange of signal interference damage control card, you must use the conversion LD-8302C module control interface。 The control card to LD-8302C module uses the promise of two-wire connection
◎ Output: this control card has 2 output, output DC24V, 80mA
◎ Using environment: temperature: 0 ° c ~ + 40 ° c relative humidity ≤ 95%, no condensation
◎ Working voltage: DC24V
◎ Using voltage range: DC20V ~ DC28V
◎ Power "1.7W
● LD-KZC-100-multi-line system CPU control card (spare)
More wire CPU control card for mould-plastic structure, and the multi-project KZK-100 wire control card matching can be used for all types of fire alarm controller, and can be used with the type of control card with KZK-100 composition dedicated multi wire system control panel.
More wire control panel as standard plug disk structure and JB-QG-GST5000, JB-QG-GST6000, fire alarm controller Assembly in the same enclosure, complete with fire and smoke machines, blowers, and other important device control. You can choose the control panel of the control points, you can control up to 14 road equipment.
This control card (disk) can be set to connect KZK-100-multi-line control card address and control card access fire alarm controller signaling bus. This control card (Pan) is a multiple-line KZK-100 control cards provide manual output control inspection lamps and other control functions.
The main technical indicators are as follows:
¡Ò control tray capacity: up to 14-channel output, each taking a bus address coding points
◎ Wires: two controller bus and two 24V power supply line
◎ Using environment: temperature: 0 ° c ~ + 40 ° c relative humidity ≤ 95%, no condensation
◎ Working voltage: DC24V
◎ Using voltage range: DC20V ~ DC28V
◎ Power consumption: 1W (CPU cards), the "25W (Control Panel)
¡Ò control plate dimensions: 484mm×178mm×74mm
● LD-8302C type conversion interface module
LD-8302C switch module is a non-encoding conversion interface module, start, stop moving two pair, normally closed output contact, according to the equipment needs to be charged. The module and multiple cable system control KZK-100 card. Control Panel switch modules through LD-8302C charged device control, and implementation and control devices, circuit breakers, short-circuit detection and strong, weak isolation capabilities.
The main technical indicators are as follows:
◎ Starting voltage: DC18V ~ DC28V
◎ Action current ≤ 80mA
◎ Output contact:
5A, AC250V or 5A, DC30V (resistive load)
3A, DC30V 3A, AC250V or (inductive load)
◎ Using environment: temperature:-10 ℃ ~ + 50 ° c relative humidity ≤ 95%, no condensation
◎ Dimensions: 120mm80mm39mm
(11) other equipment
● GST-HX-M8501/GST-HX-M8502 coding fire alarm sound/light
GST-HX-M8501/GST-HX-M8502 coding fire sound/light alarm is installed in the field of sound or sound and light alarm equipment, fire protection control center fire alarm controller initiated by manually installed in the field of alarm button started directly. After a strong start of acoustic alarms or acousto-optic alarm to remind the purpose of the field note.
GST-HX-M8501/GST-HX-M8502 coding fire alarm sound/light-fast and slow two rhythm siren, fast-paced alarm sound is high or low two sound pressure level optional, can be set by the encoder. Optical display using only super bright red LEDs as the light source, the display striking, long life, low power consumption. You can start the Alerter short external control Terminal, from power-fail signal bus.
And signal bus and power supply bus using polarity 2 convenient bus connections, wiring; with bus power off detection function, to supply bus power, fault information to the controller.
GST-HX-M8501/GST-HX-M8502 coding fire alarm sound/light base using limit design, with anti-removal function, so that the fire alarm sound/light has a unique installation location. Can electronic coding that is simple and convenient.
This device is a patented product, Patent No.: ZL 99 3 11721.X.
The main technical indicators are as follows:
◎ Operating voltage: 24V voltage bus: bus, power supply voltage: DC24V
◎ Monitor current: 1mA current ≤ bus, power supply current: 5mA
◎ Current £ GST-HX-M8501: bus current ≤ 5mA, power supply current: 50mA
GST-HX-M8502: bus current ≤ 5mA, supply current ≤ 60mA
◎ Wire: and controller-polarity signal second bus connections, you need two-polarity 24V power supply line
◎ Alarm sound pressure level: loud 85dB, low pressure level over more than 75dB (front 3m level (A weighted))
◎ Using environment: temperature:-10 ℃ ~ + 50¡æ £ ¬2 relative humidity: 95%, no condensation
◎ Dimensions: diameter: 110mm, high: 97.5mm
● BMQ-1 electronic encoder
Conventional detectors encoding you will need to manually set by mechanical dial code to complete the coding efficiency low, technical requirements, and prone to error codes, and in order to facilitate the coding, the bottom of the need to stay out of the detector coding, so easily cause detector on dust, moisture, seal the bad so that probes the overall performance of the variation.
For detectors and other equipment introduce electronic coding, operation simple, easy method (decimal). E encoding at the bottom of the detectorNo coding, tightness, also by electronic encoder, no need to probe the access controller directly on the detector performance, date of manufacture and checking of historical work data. BMQ-1 type electronic encoder can encode the electronic probes or module address number, year number, batch number, sensitivity, type number of read and write, you can display graphical fire ZF-GST8903 disk addresses, lights and the total number of each lamp corresponding quadratic codes to write and read out, the scene debugging maintenance is very convenient.
The main technical indicators are as follows:
¡Ò: Gulf company may carry out all kinds of electronic encoding detector, modules and display graphical fire ZF-GST8903 disc
◎ Working voltage: DC9V
◎ Working current ≤ 8mA
◎ Standby current: 50A
◎ Using environment: temperature:-10 ℃ ~ + 50 ° c relative humidity ≤ 95%, no condensation
◎ Dimensions: 164mm×64mm×24mm
● GST-5000 color CRT display system
GST-5000 color CRT display system is the Gulf security technology co., Ltd design by the latest generation of fire control centre fire monitoring and management system for fire alarm and fire fighting equipment management and control. Can my company produces GST200, GST500, GST5000 series fire alarm controller (joint-)-featured graphical fire Center monitoring system. Its main functions are: to build graphs monitoring Center; provides multimedia features and equipment fire, fault, action at the voice prompt; graphical display can be partial zoom, and a good guarantee that the image quality is not distorted; can be multiple controller network monitoring, the establishment of monitoring and control system for distributed network graphics.
(1) the system uses a distributed architecture that can be used in stand-alone, LAN, Internet operation. You can also manage multiple different types of controllers, multiple controller network monitor, the user can view the Internet or local area network, monitor system performance.
(2) can be done on this system and all devices control actions (start, stop, quarantine, release device, etc), provides fire alarm controller (linkage) of the same control modes, and can operate on the controller and the settings.
(3) the user can at any time through the communications test functionality test system data communication status, ensuring reliable operation of the system.
(4) when the fire broke out in the on-site equipment, the actions, failure, quarantine, in the appropriate location for the graphics flashing graphics, along with the text display, voice prompts, and so on, automatically eject the editing of the corresponding device supporting programmes in emergency situations to tips on duty to complete the necessary contingency operations. These features are very useful command field fire.
(5) simple, intuitive and complete graphical user interface, you can monitor and automatically or manually see floor equipment distribution graph.
(6) easy, intuitive and quick buttons, you can improve work efficiency, handling the exception information in a timely manner.
(7) are available through local and remote real-time print device exception information; browse system controller information, floor information, history of linking formulas, users, support for multiple conditions combined query various fire, failure, and other historical records.
(8) system provides multi-level password for system security management to prevent accidental operation.
(9) the complete database management functions, and data backup function, you can send your data loss to a minimum, ensure that your system security.
(10) provided automatic upgrading client and file download tool, able to timely update the required system files.
Labels:
[:]
Subscribe to:
Post Comments (Atom)
Thanks for sharing this extremely informative article on 3M gulf in uae. I recently read about 3M gulf on website called aiwa.ae. I found it extremely helpful.
ReplyDeleteYes, this is a good post without any doubt. You really do a great job. I am inspired by you, so keep it up!
ReplyDeleteLandscape Contractors
Yes, this is a good post without any doubt. You really do a great job. I am inspired by you, so keep it up!
ReplyDeleteMarble & Granite
Etisalat yellow pages UAE is one of the largest B2B Portal & online business directory. You can find the top verified sellers, manufacturers, suppliers, wholesalers and more businesses listed with us.
ReplyDeleteEtisalat yellow pages UAE is one of the largest B2B portal & online supplier directory. You can find the top verified sellers, manufacturers, suppliers, wholesalers and more businesses listed with us. Our website is significantly better and customized to help you grow your business and easily accessible for the visitors. A buyer can get quality products and services from certified brands that are listed with Etisalat Yellow Pages UAE.
ReplyDeleteEtisalat yellow pages UAE is one of the largest B2B portal & online business directory. You can find the top verified sellers, manufacturers, suppliers, wholesalers and more businesses listed with usyou can have the details for Supplier Directory.
ReplyDeletewow what a great post it provides me the best information but if you are looking for bussiness in uae Etisalat yellow pages UAE is one of the largest B2B portal & online business directory. You can find the top verified sellers, manufacturers, suppliers, wholesalers and more businesses listed with us find out the best Local Business Directory.
ReplyDeleteThere is a note pack to know about this. I assume you scored some good points in the features as well.audit services in abudubai
ReplyDelete