【 Weak current College 】 fire system operation standard operating procedures-Power By 【 China power house network 】
1.0 purpose
Standardized system of equipment operation
2.0 scope
Apply to the property area fire management center fire protection system of equipment operation
3.0 duties
3.1 fire management centre supervisor is responsible for the supervision and inspection of fire protection system for all types of equipment operation procedures.
Fire management centre is responsible for fire 3.2 system operation business guidance.
3.3 fire management centre firemen by this specification for the proper operation of fire fighting equipment.
4.0 program Essentials
4.1 fire host
4.1.1 acknowledgement alarm:
A) when the host receiving FS90 fire alarm, press the "silencing" alarm key elimination;
B) press the "reset" button to view the fire can reset the host to enter the system to normal status: If access to the system the normal state to prove that the alert is a false positive, press the "reset" button reset; if you cannot enter the system the normal state, proved to be a failure, or fire weather forecast, check the "State" key to confirm the AV value.
4.1.2 check status confirmation AV value (when the value is equal to 100 AV, proved to be a fire signal occurs, immediately sent to the scene to view):
STATUS-a);
B) press F1 (until you see the SD address templates);
C) address code (0-9);
D) press ENTER to enter (confirming that AV value, concentration of alarm points);
E) press CLEAR cancel (let the system back to normal).
4.1.3 fire prediction or fault alarm: (AV = 90-100, belongs to fire prediction; AV = 0--30 belonging to fault alarm. The fire prediction or failure points temporarily quarantined, lock, put the system to normal state.)
Amended by MODIFY a);
B enter password press 1234);
C) press enter Enter twice;
D) press CLEAR cancel.
4.1.4 unlock (processed fire prediction or fault alarm, the quarantined points open to let the system back in operation status);
A COMMAND instruction);
B) to enter the password 1234 select SD address templates;
Press ENTER to enter c);
D) F1 select SD address templates;
E) press code 0-9;
Press ENTER to enter f);
F3 g);
H) press F4;
Press CLEAR cancel I)
4.2 print
4.2.1 installation of printer paper:
A new paper roll) will wear on the shaft in the feed;
B) will feed the hinge placed in printers bracket;
C) will head to fold the paper in about half an inch, resulting in a flat paper head standby;
D) paper head through the photoelectric switch is installed into the printer, press the printer Panel "feed" (PAPERADVANCE) button lights, make paper head through the print mechanism;
E) continue to feed, about 12 inch standby;
F) head through the paper and connected to reclaim the hinge axis;
G) placed in the head of the paper recycling hinge slot;
H) will reclaim the hinge number ring clockwise to recycling paper.
4.2.2 Installing printer paper, such as a warning or failure, the paper will automatically print records.
Remove the paper: 4.2.3
A remove the feed axis);
B remove the paper roll core);
C) by printer Panel "feed" (PAPERADVANCE) button lights, so that the paper trail is completely out of the printer;
D) remove recovery hinges;
Remove the old e) paper archive.
4.3 fire tank fire phone, can lead to four floors (Jack) high pressure water pump room, rooms, floors view alarm point location conditions of operation.
4.3.1 the Jack phone into the holes in the fire Cabinet received sound alarm.
4.3.2 the "floor" (the water pump housing and high pressure room) key once.
4.3.3 and floor (or electrical maintenance electrician) call.
4.4 fire radio
4.4.1 fire broadcast evacuation, fire broadcasting led lights adjacent floor digital, lights.
4.4.2 power switch (forward).
4.4.3 regulating broadcasting should control the volume knob, clear, clear (counter-clockwise volume larger volume clockwise until closing volume smaller).
4.4.4 start to the floor.
4.5 fire of passenger and freight elevator
4.5.1 in the event of fire, from fire Cabinet press "down" keys to the elevator, passenger and freight elevator landing on the first floor.
4.5.2 before from passenger and freight elevator room first floor breaking glass, according to "eliminate"Open key, passenger and freight elevator will be forced to first floor.
4.6 fire pump when there is a "fire" alert
4.6.1 start automatically:
A) in the floor and for all "fire hydrant alert box", fire Cabinet beep alarm;
B) fire pump start automatically.
4.6.2 start manually:
Select a) "automatic/manual switch on the" select "manually";
Press the Start button b) "manually" started the fire pump.
4.7 spray pump when there is a "fire" alert
4.7.1 automatically start:
Spray pump is a) "automatic" position.
B) shower head, flow switch, fire Cabinet beep alarm;
C) spray head start automatically.
4.7.2 start automatically:
Select a) "automatic/manual switch on" manual "," position;
Press the Start button b) "manually" started the fire pump.
4.8 fire shutter when fire or smoke when
4.8.1 fire shutter automatically starts to receive the probe signal:
A) fire Cabinet beep alarm, fire shutter closes.
B) fire shutter closes.
4.8.2 start manually:
A) put "automatic/manual switch on the" select "manually";
B) XX floor fire shutter start button;
C) fire cabinet will beep alarm, turn off signal;
D) from the floor fire shutter switch gear down press the Start button (down to open, in the middle is stopped), the fire shutter is closed down.
4.9 stop non-fire: the fire power supply needs to be truncated from the fire Cabinet press "stop non-fire electric fire, power outage" key.
4.10 fire hydrant
4.10.1 indoor hydrants:
A after the fire) with fire box opening, with a key or hard objects break glass door;
B) press the emergency alarm button;
C) fire hydrant box red led lights, fire signal sent out;
D) fire hydrant can be directly started the fire pump water supply;
Remove the gallows on the e) connected to the tape interface water gun and connected to fire hydrants interface;
F) counter-clockwise fire hand wheel;
G) water fire extinguishing.
4.10.2 hydrant:
A fire with a special wrench) counterclockwise rotation open outlet plug;
B) connected to the water zone (gun) or suction pipe;
C) with special wrench open plug to supply;
D) should be turned off after use, the plug on good outlet plug.
4.10.3 fire plumber:
A door will open fire hydrant) volume circled out;
B) opened the rubber tube and small-calibre gun;
C) open water gate valves for fire-fighting;
D) is complete, turn off the water gate valve, hose after excluding the water, the volume of rewind up reel back to the fire box.
4.11 fire extinguishers
4.11.1 will fire extinguisher referred to the scene.
4.11.2 removed seals, pull the insurance market.
4.11.3 in fire extinguishers effective spray distance within the nozzle (or hose nozzle) alignment flame root.
4.11.4 press pressure, opened the sealed, fire extinguishing agent.
4.11.5 release pressure, intermittent spray body reset, Jet stop.
4.11.6 Jet, shall promptly forward the sway, barn fire, prevent tempering comes alive.
4.11.7 outdoor operation, you should select the poop Jet.
5.0 records
6.0 associated support files
6.1 the fire drill standard operating procedures "
6.2 fire equipment management standard operating procedures "