First, the automatic fire alarm system
1. detection of automatic fire alarm system wiring insulation resistance, resistance, system grounding, pipeline installation and its protection status;
2. detection of fire detectors and alarm button settings, installation quality, protection RADIUS and surrounding Occluder distance, etc., and by 30 ~ 50% proportional sampling its alarm function;
3. detection of fire alarm controller installation quality, inside wiring, protection, earthing and standby power settings, the settings and transformation capabilities, and controller functions test;
4. detection of fire-fighting equipment control cabinet installation quality, inside wiring, hand, automatic control and the Panel accepted firefighting equipment signal feedback function;
5. detect elevator landing capabilities, fire elevators feature, cut off the non-fire-power functions and burning layer light display;
6. detection of fire control room, the fire protection equipment and fire hydrant button Office communication;
7, testing fire emergency broadcasting of audio features, manually selected layers and automatically broadcast, remote controlled opening and forcibly switches, and other functions;
8. detecting fire control room set location and clearly marked, indoor fire damper and independent pipeline set, double-circuit power settings and switching;
9, detection of fire emergency lighting and evacuation signs set, illumination, conversion time and graphic symbols;
Second, the fire service
1. check the nature of the fire water sources, the number of pipes and the diameter of the fire pool settings;
2. check the fire water tank volume, water level indicator and water facilities, ensure fire water and frost protection measures;
3. check the settings of the fire water tank, capacity, antifreeze, water and the State of the check valve;
4. detection of various fire pump performance, pipes, hand control, start time, and reserve and standby pump and power conversion functions, etc.;
5. detection combined with the pump set, signs and conveying fire-fighting water features, etc.;
3, indoor hydrant system
1. check the indoor hydrant installation, Assembly, specifications and spacing, etc.;
2. test the settings, the roof of a fire hydrant frozen Chan and enrich the water column length measures, etc.
3. check the settings of the indoor hydrant pipeline, pipe diameter, colors, ensure fire water and connect shapes;
4. detection of the first floor indoor hydrant and the most negative point of static and dynamic pressure and enrichment of the water column length;
5. check the manually restart the pump button's settings and functions;
4. automatic water spray (fog) fire control system
1. check the network install, connect, set the number to the end of the nozzle and pipe diameter, etc.;
2. check the flow indicator and signal valve installation and function;
3. detection alarm valve group status of the installation, valve, various components and their functions;
4, detection spray head installed, appearance, protection and conservation area and the distance with nearby obstructions;
5. alarm function test valve sets;
6. automatic spray water (fog) system for functional test;
Fifth, smoke and air conditioning system
1. check the positive pressure air supply systems wind pipe, fans, air condition and measuring its set speed and value the positive pressure ventilation;
2. detection of smoke exhaust system fans, air, fire, air, and standby power settings and functions;
3. check the ventilation and air-conditioning system of the pipeline and fire damper setting conditions;
4. on the various systems for manual, automatic and linkage function test;
Six, fire doors, fire shutter and smoke vertical wall
1. on its appearance, installation, drive mechanism and action programs and manual and linkage function for detection;
7. gas fire extinguishing system
1. check the gas fire extinguishing system storage device between a bottle, components, extinguishing pipes and nozzles and protection zones set up and installation conditions;
2. gas extinguishing system simulation for the linkage experiment, view to the sound of the alarm after glow, procedures, and view the cut scene of power, auto-start, delay startup volume, fire valves and blower, injection process, gas emissions indicator, actions properly.
Electrical fire detection conditions, methods and content
First, the basic electrical fire detection conditions
1, should be in the electrical installation and wiring by 1h above-load operation, on entering the heat-stable State for detection and measurement.
2. should the client side for technicians on site support.
Second, the main electrical fire detection tools
The use of modern high-tech equipment, such as infrared thermometer temperature measurement, infrared TV scan, infrared camera shoot hot spectrogram and the use of ultrasound detectors measuring abnormal temperature, spark discharge and other phenomena and use conventional electric instruments, instruments such as voltmeters, ammeters, electroscope, grounding resistance tester, TRMS ampere meter, etc, on the operation of the electrical facilities of various operating parameters for measurement and use of Visual methods, control the relevant technical specifications, to run in high-voltage electrical equipment installation, use, maintenance, and maintenance of electric fire detection.
3. check (logging)
1, the transformer room
① Visual inspection of the set transformer room location, fireproof grade and hole sealing; transformer set, Visual quality, components, integrity and fire prevention measures; high-voltage cable (wire) installation, etc.
② with infrared thermography transformer windings and high-low cable (wire) contact temperature and beat the heat map.
2, high (low) voltage distribution equipment
① Visual inspection, high (low) pressure distribution equipment settings, installation quality, inside wiring, high (low) voltage cable (wire) connector, complete grounding, accessories and fire prevention measures, etc.
② with conventional instruments to measure each phase line voltage (flow) value, N lines of unbalanced current value, PEThere are no abnormal current line and the grounding resistance values, etc.
Û infrared series instruments measuring wire and connection points, switch contact temperature and beat the heat map.
3. low-voltage power distribution box (spare)
① Visual inspection distribution box (spare) settings, material quality, installation quality, inside wiring, wiring terminal connection, Earth and fire prevention measures, etc.
② with conventional instruments measuring load current value, N line current value and there are no exceptional PE line.
Û infrared series instruments measuring box (spare) in the Terminal, the circuit breaker contact temperature and beat the heat map; the use of ultrasonic detector measurement has no spark discharge phenomena.
4. laying low-voltage distribution lines
Check the different places of power concealed, downlead, direct deposit and wear protection pipe line in the installation of electric fire hazard. 5, electrical lighting
Check the different places with electricity, a variety of lighting equipment in the installation of electric fire hazard.
6, switch, socket
Check in different places of installation of electricity, use of switches, outlets, electrical fire hazard exists.
Fire facilities maintenance content
This Center is the responsibility of running through the repair, maintenance of automatic fire alarm, sprinkler, fire hydrant, fire shutter, gas fire extinguishing systems, so that it is in a good and effective State. In peacetime to play the role of prevention, alarm, fire, timely alerts, cut off the power to isolate the source of fire, evacuation notices, fight fires, resolve customer concerns
Fire training
1. fire-fighting equipment in use such as: Manual alarm button, fire extinguishers, fire hydrant.
2. be familiar with to understand the composition of the fire-fighting system, function and role.
3, to be trained in understanding and mastering the fire alarm equipment operation and use
Fire protection engineering
Affordable automatic fire alarm systems, sprinkler systems, fire hydrant system, public broadcasting system, gas fire extinguisher system, safety engineering and fire protection engineering installation and construction.
Fire detector maintenance cleaning
Fire detector cleaning using the national key scientific research departments in the development of domestic and foreign latest technology and equipment, a good humidity and temperature control and measures against static electricity, modern cleaning technology, advanced cleaning equipment. Cleaning process using high-purity water as the medium, the ultrasonic cleaning process, closed-cycle system almost no pollution to the environment, while at the same time introduce and develop each kind of detector detection instruments, to ensure the quality of the detector after cleaning up the State page〈 GB50166 — 74G > standards.