Thursday, February 23, 2012
【 Weak current College 】 automatic fire-fighting facilities maintenance management
I. composition of the automatic fire fighting facilities
1, automatic fire alarm system
(1) trigger — manual fire alarm button, fire detectors
(2) alarm-fire alarm controller, fire monitors
(3) fire control devices — fire radio, smoke control equipment, etc.
(4) power — the main power and standby power supply
2, fire extinguishing system – shower, gas, etc.
Second, the basic requirement of maintenance management
1. the use of automatic fire-fighting units must have a system as-built drawings, equipment, technical information, instruction and commissioning report, completed reports file information, and the fire qualified acceptance.
2. the system must be put in place a strict management system. Including system operation rules; system operator fire duties; Watch system; system periodically checks, maintenance, maintenance of the system; managers regularly check the implementation of the system.
3, must be equipped with a strong sense of responsibility, have higher education level and expertise of personnel responsible for system management and maintenance, and other personnel shall not be arbitrarily touch device.
4, operation, maintenance staff should be familiar with automatic fire-fighting facilities of major performance, working principle and practice, this unit automatically fire facilities set should be well acquainted, and professional training to obtain the certificate, the certificates.
5. it is essential to the establishment of automatic fire-fighting facilities run archives, in accordance with the relevant regulations, fill in the class record. Discovery questions to timely reports on this unit.
6. in order to ensure the automatic fire-fighting facilities of continuous uptime and reliability, the units should establish a regular maintenance and inspection system, and consistently implemented.
7, fire detectors in running two years later, you should do a thorough cleaning, poor environmental conditions for the use of fire detectors shall annually conduct a comprehensive clean. After cleaning and maintenance of fire detector response value test individually.
3. automatic fire-fighting facilities specific acceptance check
(A) automatic fire alarm system
1, fire power equipment power supply automatic switching device, should switch test three times, each time correctly.
2. fire alarm controller function examination requirements.
Check all of the following 5 bed, 6 ~ 10 check 5 sets, more than 10 units, according to the actual check 30 percent to 50 percent, but not less than 5, check the basic functions of test 1 ~ 2 times.
3. fire detectors (including manual alarm button) simulation response test and fault alarm sampling. Only the following number 100, check 10; more than 100, only 5 percent smoked by real ~ 10, but not less than 10 sampling. Sampling should be fine.
4. check the indoor hydrant
Pressure should be normal, Layer 7 ~ 13 meters tall 24 ~ 50 m high is not less than 10 meters, more than 50 meters of not less than 13 m (full water column). Working pump, spare pump conversion run 1 ~ 3 times, fire control room operation restart, stop 1 ~ 3 times, the fire hydrant Kai pump button 5 percent to 10 percent of spot checks, the call control features, signal correctly.
5, automatic sprinkler systems of sampling and testing
Working pump and spare pump conversion run 1 ~ 3 times, fire control room operation restart, stop 1 ~ 3 times, water meters, valves and electric valve closed by 10 percent to 30 percent proportion test at the end on the water. Call control features good signal.
6, halides, foam, carbon dioxide, dry chemical extinguishing systems of sampling and 20 ~ 30, manual startup and emergency shut-off test for 1 ~ 3 times, and set the linkage of other fire-fighting equipment (close fire doors and Windows, stop air-conditioning fans, closing fire damper, fire curtain falls) test 1 ~ 3 times. Pumping a protection zone for spray-and-drop test (you can use gas test).
7, the electric fire doors, fire shutter of sampling, by 10 percent to 20 percent of inspection, control, signal should be fine.
8, ventilation and smoke control equipment (including fans and valve) inspection by 10 percent to 20 percent.
9, fire elevator for 1 ~ 2 times manual control and automatic control and inspection.
10, fire broadcasting equipment inspection by 10 percent to 20 percent of the function test. In fire control rooms in the selected layer broadcast, shared by the speakers forced switch test, requiring control functions properly, the voice should be clear.
11, fire testing of communication devices.
Fire control rooms and equipment between the intercom phone for 1 ~ 3 times call test; telephone jacks 5 percent to 10 percent for an outside line call test; telephone and 119 phone test 1 ~ 3 times. Not qualified to fix, proportion of unqualified double sampling and testing requirements.
IV. fire control rooms to periodically check the
(A), daily periodic check fire controller features, complete run and controller, check the registration form, the system is running, check the registration form, controller, check the registration form.
(2), quarterly should examine and test the fire alarm system, according to stipulates the following function format quarter registration form.
1, using special instrumentation test batches and confirmation of motion detector light show.
2, test fire alarm sound and light show.
3. test flow indicators, pressure switch, alarm function, signal display.
4, on standby power supply for 1 ~ 2 times charge and discharge test, 1-3 times the main power and standby power supply automatic switching test.
5, with manual or automatic checks the following fire control devices of the control display.
(1) smoke control equipment (half year 1) electric fire safety valve, electric fire doors, fire shutter control device.
(2) fire hydrant, fire sprinkler system control device.
(3) halides, foam, carbon dioxide, dry chemical extinguishing systems such as set of control equipment.
(4) fire radio, fire lighting and evacuation signage lights.
6, mandatory fire elevator stopped on the first floor.
7, fire communications equipment should be in the fire control rooms for intercom call test。
8. check all switch.
9, forced off the non-fire power function test.
(3) each year on the function of automatic fire alarm system should be the following inspection and testing, and fill out the registration form of the annual inspection.
1. annual applying dedicated testing instruments for the installation of the detector test 1.
2, in addition to the detectors, fire alarm equipment checks, all of the content of the quarterly check gas simulation test.
3, test fire radio device capabilities.
(4) detector running after 2 years, 3 years should all cleaning 1 x, and should do in response thresholds and other necessary functions. Qualified to use.
Saturday, February 18, 2012
【 Weak current College 】 new fire protection law interpretation (1)
The revised law on fire People's Republic of China (hereinafter referred to as new fire protection law) is the eleventh session of the Standing Committee examined and adopted, since May 1, 2009. The Ministry of public security official responsible for 19 new keywords for comprehension fire protection law.
New fire prevention principles
New fire law inheritance and development of our fire legal construction results in the General provisions of the "fire work in carrying out prevention, anti-binding approach, in accordance with government departments unified leadership, according to the regulation, the unit responsible for the active participation of citizens, the principles of responsibility, fire safety, establish and perfect the socialization of fire work network" and established the fire policies, principles, and accountability.
Fire safety is the governmental social management and important elements of public service, is the social stability and economic development of important protection. Governments must strengthen the leadership to fire, which is implementing the scientific development concept, building a modern service-oriented Government, building a harmonious socialist society. The relevant government departments for fire service joint management, it is fire work socialization attribute. All levels of public security, construction, industry and commerce, quality monitoring, education, human resources, and other departments should be based on relevant laws, regulations and policies, to carry out the appropriate fire safety duties. The units are the basic unit of society is at the heart of fire safety management. Citizens is the basis for the fire service, not the broad masses of the people involved in the fire service does development progress, and the whole society resist fire Foundation will not be secure. "The Government" and "sector" and "unit" and "citizens" who are the subject of the fire service, government departments, the unified leadership of supervision, the unit responsible for active participation, civic building fire safety work pattern, either party is very important, be dispensed with, this is a new fire protection law determines that the principle of work of fire.
Government fire duties
New fire protection law under article 3: "the leading national fire safety work. Local governments are responsible for the administrative region of the fire. "This is about the people's Governments at various levels in accordance with the rules of the fire work responsibilities.
Fire safety relationship people live and work, social stability and economic reform and development of the construction, relationship, job stability is important for fire work. The State Council as the Central People's Government, the highest organ of State authority, the national administrative authorities, leading national fire safety work. At the same time, the fire service is also a local strong government administrative work, many of the specific work, must be determined by the local government. New fire in macroeconomic planning, fire prevention, fire prevention, fire in rural organization construction, supervision of fire-fighting and rescue, law enforcement, Government, such as specific fire work responsibilities are clearly defined.
Police and fire agencies responsibilities
New fire protection law article 4 provides: "the public security department under the State Council on the implementation of the national fire work supervision. The local people's Governments at or above the county level public security organs of the administrative region shall exercise supervision over the management of fire prevention and fire at people's public security organs of the body responsible for implementation. ”
New fire protection law on police and fire agencies in promoting education, supervision and enforcement, fire fighting and rescue, team building, honest, and so prescribes.
New fire service law, police and fire agencies in fire in abuse, neglect their duties, commit, not the Constitution crime, legally imposes the sanction.
Fire Management main exceptions
New fire method to clear the fire services of public security organs on the specific implementation of fire prevention, supervision and control of some special units of fire prevention in the regulatory body to do the exceptions, the General provisions of article IV, paragraph 1: "the fire of military facilities, and by its competent administration units, police and fire agencies assist; mine underground parts, nuclear power plants, offshore oil and gas facilities, fire prevention, supervision by the authorities. "At the same time, forests, grasslands, the particularities of the fire service provides" laws, administrative regulations for forest, prairie fire work otherwise stipulated. ”
Administrative departments of the fire service duty
New fire protection law article 4, paragraph 2: "the people's Governments at or above the county level and other relevant departments within the scope of their functions, in accordance with this law and other relevant laws and regulations do fire safety work. ”
New fire protection law provides education, human resources administration departments and schools, vocational training institutions should be fire knowledge into education, teaching and training content. The construction of fire design without legal audit or audit non-qualified, responsible for approving the construction license for the sector of construction permits shall not be given. Provides product quality supervision departments, industrial and commercial administrative departments shall, in accordance with the mandate to strengthen the fire protection products quality supervision and inspection; production and sales of fire products or countries explicitly eliminated fire products by product quality supervision departments or the administrative authority for industry and commerce in accordance with the People's Republic of China product quality law "provisions of a heavier punishment.
Flat fire safety responsibilities
Units are the basic unit of fire management, units on fire safety and disaster management capacity factors reflect community fire safety management level, largely determine a city, an area of fire safety situation. New fire protection law and further strengthen the organs, organizations, enterprises, institutions and other organizations in support of fire safety, fire safety duties clearly in charge of the unit responsible for fire safety.
New fire protection law provides that no entity should be free to provide convenient, does not have alarm stop alarm, no fake fire; fire units, must immediately organized forces fighting fires, adjacent units should be given support; fire extinguishing, fire units and related personnel shall in accordance with the police and fire agencies require protection field, accept the accident investigation, providing and fire accurately.
BR > citizens ' rights and obligations
Citizens is an important participant in the fire service and supervision. New fire protection law on citizens in the fire in the rights and obligations are:
Anyone have the maintenance of fire safety, fire protection, fire-prevention facilities, the report fire. Any adults have participated in organized fire suppression work obligations.
A person shall not damage, misappropriation, or unauthorized dismantling, deactivate fire facilities, equipment, not to bury, occupy, blocking the fire hydrant or occupied, shall occupy, jams, closed evacuation channels, safe, fire trucks channel.
Any person found fire should immediately call the police. Anyone should be free to alarm shall not obstruct, the police. No false alarm.
Fire fight, related personnel shall in accordance with the police and fire agencies require protection field, accept the accident investigation, providing and fire accurately.
Construction project implemented fire review, acceptance and record inspection system
To reduce administrative matters, it is necessary to meet the convenience Limin, new fire protection law reform of the construction works fire management system clearly the construction engineering fire design review, acceptance and registration spot fire protection system.
New fire Act on Public Security Department's large, personnel are crowded places and other special projects, from police and fire agencies implementing construction engineering design reviews, fire acceptance.
New fire protection law clarified other project implementation record inspection system. Provisions on other projects, construction unit should be legally obtained construction license of seven working days, will fire design document reported the fire services of public security organ for the record, the public security organs fire agencies should spot checks by sampling in accordance with the law is not qualified, the construction should be stopped. Construction unit after the engineering acceptance should be reported to the police and fire agencies for the record, the public security organs fire agencies should spot checks by sampling in accordance with the law, not qualified to be suspended.
Public gathering places for fire safety check
Public gathering places for fire safety has always been the focus of fire management. New fire law inheritance and developed the original fire protection law on police and fire agencies on the public gathering places in use, business before the fire safety inspection, canceled the original fire protection law regarding public gathering places without fire safety inspection or examination does not comply with fire safety requirements for the unauthorized use, business administrative punishment, corrected within a precondition, to the existence of such violations, and provides for direct to order the cessation of construction, stop use and halt the administrative penalties and fines.
Organizing mass events fire safety requirements
To reduce administrative matters, new fire protection law will be a large mass of fire safety into the large mass activities, safety management regulations and order of an administrative review of the content, avoid multiple approval to facilitate community to facilitate the masses, and at the same time, clear the fire safety requirements to organize major mass activities, the sponsor shall apply to the public security organs to develop safety permit fire fighting and emergency evacuation plan and organize the walkthrough, the clear division of responsibilities for fire safety, fire safety management personnel, maintaining fire protection equipment and fire-fighting equipment configuration is complete, intact, ensure evacuation channels, safe export, evacuation signs, emergency lighting and fire trucks channel meets the technical standards and regulations.
Fire product supervision and management system
Fire products belong to security products, their quality is directly related to the fire of fire protection products can effectively play its role to protect the personal safety and property security. New fire protection law further defined the monitoring and management system of fire protection products. Provision of fire protection products must meet national standards; there is no national standards must be consistent with industry standards. Prohibiting the manufacture, sale or use of products and countries explicitly eliminated fire protection products.
New fire protection law identified fire products compulsory certification system, the provisions of the law should be a mandatory product certification of fire protection products, by a legally qualified certification bodies in accordance with national standards, industry standards mandatory requirements for certified before production, sale and use.
Thursday, February 16, 2012
【 Weak current College 】 new fire protection law interpretation (2)
Urban planning changes to town and country planning
In recent years, rural fire safety situation remains very serious, the fire occurred, loss and casualties high fire safety in the village. New work from fire fire protection law, the adaptation of global and building new Socialist countryside, at the request of a harmonious society, dedicated to rural fire service, specific provisions identified local governments should strengthen rural fire service leadership, to take measures to strengthen public fire facilities construction, the Organization establish and supervise the implementation of responsibility for fire safety.
New fire protection law will be the fire method of "urban planning" was changed to "urban planning", "local people's Governments at all levels should include fire safety layout, fire station, fire service, fire, fire engines, fire equipment, fire planning into town and country planning, and is responsible for organization and implementation. Urban-rural fire safety layout does not comply with the fire safety requirements, it should be adjusted, perfect; public fire-fighting, fire protection equipment, inadequate or not adapted to actual needs, should be built, rebuilt, configuration or technical renovation ". A word of variable, "City" and "rural", reflects the work of the rural fire.
Construction of multiple forms of fire power
Fire prevention practice shows that the establishment of various forms of fire power is determined by China's national conditions, is the development and protection of the essential foundation of people's livelihood is well-off social requirement.
New fire law inheritance and development of a completely original fire services law relating to the construction of many forms of fire forces the creation of multiple forms of fire forces the overall requirements, the distinction between cities, towns, explicit construction of different forms of fire power requirements. Provisions of the "people's Governments at or above the county level shall, in accordance with national provisions on the establishment of public security fire fire brigade, allied, and in accordance with the national standard are equipped with fire-fighting equipment, fire fighting work. Township government shall, in accordance with the local economic development and the need for fire prevention, establish a full-time volunteer fire department, fire department, fire suppression work. "
Bear emergency rescue work
The 17th CPC National Congress proposed the "perfect emergency rescue system" requirement, which is to protect our country's economic and social development, security, development of important strategic tasks. Fire brigade as the maintenance of public security forces to bear many emergency rescue work, this is the common practice in the countries of the world and the development trend of the international community.
According to our emergency rescue force construction of actual needs, take full account of the fire brigade in active systems, equipment, training, management, and other advantages, as well as in recent years, the fire brigade emergency rescue work results, new fire protection law further strengthened by the fire brigade and Government allied fire brigade emergency rescue capacity-building and the necessary safeguards to provide public security fire service, Government, professional fire brigade in accordance with State regulations assume major disasters and other emergency personnel life-based emergency rescue work.
Specialized supervision "increase"
Have the right to have the responsibility, authority, infringement of the right to compensation, it is illegal to pursue, in accordance with the administrative and establish the rule of law and Government, responsible government requirement. In order to strengthen the fire protection supervision, new fire protection law specifically add "supervision" chapter, focus on norms and constraints on Government and Government departments, in particular the police and fire agencies exercise of the powers and strengthening of its supervisory duties according to law, the police and fire agencies supervise management also raised higher and more stringent requirements.
Perfect fire administrative sanction system
New fire protection law adapted to the needs of the development of the fire service, the relevant provisions of the legal responsibilities on a larger amendment to increase the intensity of the fire administrative sanction, supplementary improve fire administrative sanction system.
New fire protection law increases should be administrative punishment of violations of fire-fighting regulations of the Act, a solution to the original fire protection law for violating fire regulations do not provide full, not tight, some of the violations are not promptly halt, correct and punished according to law, maintain the seriousness and authority of the law.
New fire protection law adjusting the types of administrative penalty. New fire protection law set the warning, a fine, detention, be ordered to cease (stop construction, stop use), confiscation illegal obtained, be ordered to stop practising (revocation of the corresponding qualification, qualification) six types of administrative penalties, increased order ceased to practise (revocation of the corresponding qualification, qualification), a kind of administrative penalty on a number of serious violations of fire-fighting regulations of the Act in particular acts of endangering public safety an additional penalty of detention, the law of the deterrence.
New fire safety violations
New fire protection law new fire violations are: (1) fire design via public security fire agencies according to the random unqualified, not stop construction; (2) a construction works in use by police and fire agencies representing non-qualified according to the law, do not stop using; (3) construction units not legally will fire design document reported the fire services of public security organ for the record, or failing to report after the completion of public security fire agencies for the record; (4) the construction of the building design unit or building construction enterprises reduce fire technical standards for the design, construction, and (5) construction and design units do not follow the fire technical standards mandatory requirements for fire protection design; (6) construction supervision units and construction units or collusion, falsification of construction enterprises, construction quality to reduce fire; (7) the personnel-intensive sites in door and window effect escape and set on fire-fighting and rescue of obstructions; (8) production, storage and management of inflammable dangerous places and living place settings in the same building, or not and keep a safe distance from the place of residence; (9) the production, storage, operation and other items of place and a place to live in the same building that do not meet the technical criteria for fire fighting; (10) the illegal carrying flammable explosive hazard access to public places or by public transport; (11) hinder police fire agency personnel from legally performing their official duties; (12) in the fire stop alarm, or have reporting responsibilities of staff not timely alarm; (13) the unauthorized use of the seal or by publicAn Office fire agencies place, parts of sealed; (14) the personnel-intensive sites use unqualified fire products or countries explicitly eliminated fire products; (15) fire product quality certification, fire detection, fire technical facilities services agencies provide false, inaccurate file.
These acts, there is a fire works adjusted the new situation, some socio-economic development of the new situation, new problems, there is the recent serious fire accidents of highlight, there are also more prominent, the greater danger. Therefore, the provisions of the new fire protection law should be given to the corresponding administrative punishment.
Increase in temporary seizure measures
New fire protection law in the original fire legislation concerning compulsory measures on the basis of the practice of law enforcement, fire fighting increased temporary closure measures.
New fire law police fire agencies in fire inspection found the fire danger, it shall notify the entity or individual to take immediate steps to eliminate risks; not timely elimination of hazards may be a serious threat to public safety, police and fire agencies should follow the provisions on dangerous sites or places of temporary closure measures.
Police station fire supervision duties in accordance with the provisions of the
Our more than 60% of fires and more than 60% of fire deaths and injuries occur in rural areas and towns. Considering that the public security organs fire agencies only in people's Governments at or above the county level, and the public security organs established police station covering the vast rural areas and urban communities, new fire protection law gave the police station, fire supervision duties require police station can be responsible for the day-to-day supervision and inspection of fire protection, fire safety education and awareness.
Tuesday, February 14, 2012
【 Weak current College 】 Gulf equipment technical characteristics and parameters (1)---Power By 【 China power house network 】
Table of contents
(A) fire alarm controller 1
● JB-QT-GST5000 type control center fire auto-alarm host 1
● JB-QG-GST5000 type Control Center 3 automatic fire alarm host
● JB-QB-GST500-type fire alarm controller (linkage) 5
● JB-QB-GST200-type fire alarm controller (linkage) 7
(Ii) fire detector 9
● JTY-GD-G3 type intelligent photoelectric smoke detector 9
● JTW-ZCD-G3N type intelligent electronic differential fixed temperature heat detector 11
● JTY-GF-GST104-non-coding photoelectric smoke detector 12
● JTWB-ZCD-G1 (A) non-encoded electronic differential fixed temperature heat detector 12
● BT-KVA001 coding combustible roof household 13
● BT-KVA002 coding combustible wall-mounted home 14
● JTY-HS-G2-smart style infrared beam smoke detector 15
● JTW-LDB-100 type intelligent cable type heat detector 16
● JTG-ZW-G1-smart 17 UV flame detector
● JTF-GOM-GST601 type intelligent gas temperature composite detector 18
● JTGB-ZM-GST501/I/I-type explosion-proof 19 UV flame detector
(3) alarm buttons 20
● J-SAP-8401-manual fire alarm buttons 20
● J-SAP-8402-manual fire alarm button (with the phone jack) 21
● LD-8403-intelligent code 22 fire hydrant alarm button
● LD-8404 type intelligent encoding fire hydrant alarm button 23
(4) onsite module and interface device 24
● LD-8300-monitoring module 24
● LD-8301-Smart encoding for single-input/single-output module 25
● LD-8303 intelligent encoding two-input/output modules-26
● LD-8304 coding fire phone module 27
● LD-8305 coding fire radio switch module 27
● LD-8311-bus 28 relay fiber interface
● LD-8313-bus isolator 29
● LD-8319 coding repeaters 30
● LD-8320 active Terminal 31
(5) fire displays disc 32
● ZF-101 fire displays disc 32
● ZF-500 type Chinese character LCD display disk 33 fire
● ZF-GST8903-graphical fire show tray 34
(6) power 35
● GST-DY-100-type power supply box 35
● GST-DY-200 type intelligent power supply unit 36
● GST-LD-D02-intelligent power plate 37
(VII) fire broadcasting system 38
• Bus system fire emergency broadcasting system 38
«More wire fire emergency broadcasting system is 39
(8) fire telephone system 40
• Bus system fire telephone system 40
«More wire fire telephone system 41
(9) 42 gas fire control
● LD-QKP06 type gas fire extinguishing control plate 42
● Gas extinguishing control card 43
● LD-8317A-gas spray led 44
● LD-8318A-emergency stop-button start/45
(10) many wire linkage control device 46
● KZK-100-multiple wire control card 46
● LD-KZC-100-multi-line system CPU control card (spare) 47
● LD-8302C type conversion interface module 48
(11) other devices 49
● GST-HX-M8501/GST-HX-M8502 coding fire alarm sound/49
● BMQ-1 electronic encoder 50
● GST-5000 color CRT display system 51
Equipment performance characteristics
GST licensing distribution intelligent fire alarm and fire control system is the Hudson Bay Company successfully developed high-tech fire electronic products, the technology mature, their performance characteristics are as follows:
(A) fire alarm controller
● JB-QT-GST5000 type control center fire auto-alarm host
Design uses JB-QT-GST5000 type Chinese character LCD display fire alarm controller (linkage) as the control center alarm controller, its main characteristics are as follows:
Big-screen liquid crystal display Chinese characters, various alarm status information can be intuitive to Chinese characters are displayed on the screen to make it easy for users to use; you can observe the work of an intelligent dynamic probes for curve for the scene of actual environmental conditions; controller with powerful Panel control and operating functions, a variety of feature comprehensive, simple and convenient.
The controller has a modular design, highly intelligent features, together with the smart probe composition distribution intelligent fire alarm systems, systems of work high reliability and greatly reduces false positives.
System internal parallel bus data transfer, the main control board and the circuit board for information transmission between a query, it would not affect multiple loop machine inspection speed, fast, accurate information transmission.
All bus control system wiring flexibility, you can use alarm point and linkage point total circuit wiring, wiring simple; you can also use alarm point and linkage dotted circuit wiring methods, systems, and high reliability.
The controller has a very strong field programming capability, the loop device interdisciplinary collaborationDynamic and diverse character information note, bus system control devices and much line control devices, such as the linkage between can live programming.
The controller can be completed automation and manual control of the external fire-fighting equipment, which is charged with manual control mode with direct manual control of the output and the encoding key combinations manually control output method, any address within the code point can be occupied by a variety of encoding detector or by the use of various encoding module, design flexibility. Linkage control equipment use 24V DC power supply, making interaction device failure will not affect the normal work of the host.
The main technical indicators are as follows:
◎ LCD size: 320 × 240 graphic dot matrix, you can display Chinese characters 12 rows
◎ Controller capacity:
A. system capacity expanded to 40 block 242 address coding circuit for a maximum capacity of 9680 addresses coding points.
B. external 64 fire show up; interconnection maximum 32-other types of controller.
C. multiple wire control points and direct manual control can bus requires configuration.
◎ Wire:
A. controller and detector using polarity signal second bus connections, and each kind of control modules in addition to the promise of 2 bus out, plus two DC24V power bus.
B. and the other type of controller using polar II bus connection, fire warning shows up, plus two DC24V power bus.
C. color CRT system uses four-core flat telephone line connection through RS-232 standard interfaces, maximum length should not exceed 15m connector.
◎ Using environment: temperature: 0 ° c ~ + 40 ° c relative humidity ≤ 95%, no condensation
¡Ã’ main power for power: AC 220V; controller by electron DC24V24Ah sealed lead battery; electric as prepared by the linkage DC24V24Ah sealed lead batteries.
◎ Power consumption ≤ 150W
◎ Dimensions: 1080mm×1113mm×1350mm
◎ Bus communication distance 1.5 km
◎ Have RS-232, and RS-485 interface
● JB-QG-GST5000 type control center fire auto-alarm host
Design uses JB-QG-GST5000 type Chinese character LCD display fire alarm controller (linkage) as the control center alarm controller, its main characteristics are as follows:
Big-screen liquid crystal display Chinese characters, various alarm status information can be intuitive to Chinese characters are displayed on the screen to make it easy for users to use; you can observe the work of an intelligent dynamic probes for curve for the scene of actual environmental conditions; controller with powerful Panel control and operating functions, a variety of feature comprehensive, simple and convenient.
The controller has a modular design, highly intelligent features, together with the smart probe composition distribution intelligent fire alarm systems, systems of work high reliability and greatly reduces false positives.
System internal parallel bus data transfer, the main control board and the circuit board for information transmission between a query, it would not affect multiple loop machine inspection speed, fast, accurate information transmission.
All bus control system wiring flexibility, you can use alarm point and linkage point total circuit wiring, wiring simple; you can also use alarm point and linkage dotted circuit wiring methods, systems, and high reliability.
The controller has a very strong field programming capability, the circuit cross-linkage between devices, various Chinese character information note, bus system control devices and much line control devices, such as the linkage between can live programming.
The controller can be completed automation and manual control of the external fire-fighting equipment, which is charged with manual control mode with direct manual control of the output and the encoding key combinations manually control output method, any address within the code point can be occupied by a variety of encoding detector or by the use of various encoding module, design flexibility. Linkage control equipment use 24V DC power supply, making interaction device failure will not affect the normal work of the host.
The main technical indicators are as follows:
◎ LCD size: 320 × 240 graphic dot matrix, you can display Chinese characters 12 rows
◎ Controller capacity:
A. system capacity expanded to 40 block 242 address coding circuit for a maximum capacity of 9680 addresses coding points.
B. external 64 fire show up; interconnection maximum 32-other types of controller.
C. multiple wire control points and direct manual control can bus requires configuration.
◎ Wire:
A. controller and detector using polarity signal second bus connections, and each kind of control modules in addition to the promise of 2 bus out, plus two DC24V power bus.
B. and the other type of controller using polar II bus connection, fire warning shows up, plus two DC24V power bus.
C. color CRT system uses four-core flat telephone line connection through RS-232 standard interfaces, maximum length should not exceed 15m connector.
◎ Using environment: temperature: 0 ° c ~ + 40 ° c relative humidity ≤ 95%, no condensation
¡Ã’ main power for power: AC 220V; controller by electron DC24V24Ah sealed lead battery; electric as prepared by the linkage DC24V24Ah sealed lead batteries.
◎ Power consumption ≤ 150W
◎ Dimensions: 580mm×520mm×1873mm
◎ Bus communication distance 1.5 km
◎ Have RS-232, and RS-485 interface
Sunday, February 12, 2012
【 Weak current College 】 Gulf equipment technical characteristics and parameters (3)
● JTW-ZCD-G3N type intelligent electronic differential fixed temperature heat detector
Smart electronic differential fixed temperature heat detector using high-quality electronic temperature sensors as well as a dedicated control chips and digital bus communication technology, stable performance, reliable. Probes according to application environment can be individually set to differential temperature or fixed temperature detector, and you can set the sensitivity of the differential temperature detector and a fixed temperature detector of alarm temperature to apply different places for the application.
Detectors can bus, annular or two ways mixed cabling and automatic fire alarm controller connected wiring flexibility, ease of installation.
Detector design takes full account of the characteristics of the waterproofing. The entire probe into the cradle and the detection of the first two parts, the cradle only fixed pin terminals, not including other circuits. Detector, with sealed bottom side with overflow hole; terminal block design with waterproof jacket protection, ensure that there is water or water seepage of the spill, the detector can work properly. This probe can be carried out through the handheld electronic coding encoder and performance checks, has good resistance to dust and moisture.
This detector is a patented product, patent number ZL99311722.8.
The main technical indicators are as follows:
◎ Operating voltage: 24V bus
◎ Monitor current ≤ 0.8mA
◎ Alarm current ≤ 2.0mA
◎ Alarm acknowledgement lamp: Red flashes when the inspection, the alert always lit
◎ Fixed temperature sensitivity level: fixed temperature sensitivity level 1: alarm setting temperature of 58 degrees centigrade; fixed temperature sensitivity level 2: alarm setting temperature 66 degrees centigrade; fixed temperature sensitivity level 3: alarm setting temperature 72 ° c.
◎ Using environment: temperature:-10 ℃ ~ + 50 ° c relative humidity ≤ 95%, no condensation
◎ Encoding: decimal electronic coding
◎ Dimensions: diameter: 100mm, high: 45mm (without base)
● JTY-GF-GST104-non-coding photoelectric smoke detector
With a new type of scattering technique and imports of optoelectronic devices and improves the reliability of the sensor, the stability and consistency, and a unique maze design, pest control, dust-proof, resistant to external light interference. Product novel structure, appearance, performance stable reliable, strong resistance to moisture, and has a good resistance to chemical corrosion. This detector alarm mode for the current type, with LD-8319 coding repeaters, LD-8320 active Terminal, you can access the company's production of various types of fire alarm controller, complete the detector signal processing.
The main technical indicators are as follows:
◎ Operating voltage: DC12V ~ DC28V
◎ Monitor current ≤ 60 μ A
◎ Alarm current: 10mA ~ 30mA
◎ Alarm acknowledgement, alarm lamp: Red often lit
◎ Using environment: temperature:-10 ℃ ~ + 50 ° c relative humidity ≤ 95%, no condensation
◎ Dimensions: diameter: 100mm, high: 42mm (without base)
● JTWB-ZCD-G1 (A) non-encoded electronic differential fixed temperature heat detector
JTWB-ZCD-G1 (A) non-encoded electronic differential fixed temperature heat detector is the use of temperature-sensitive components of sensitivity to detect the temperature, the built-in MCU, curing the high reliable fire judgment proceedings and with the special craft processing, stable and reliable, and has good resistance to chemical corrosion. This detector alarm mode for the current type, with LD-8319 coding repeaters, LD-8320 active Terminal used to access the company's production of various types of fire alarm controller, complete the detector signal processing.
The main technical indicators are as follows:
◎ Operating voltage: DC12V ~ DC28V
◎ Monitor current ≤ 60 μ A
◎ Alarm current: 10mA ~ 30mA
◎ Alarm acknowledgement, alarm lamp: Red often lit
◎ Using environment: temperature:-10 ℃ ~ + 50 ° c relative humidity ≤ 95%, no condensation
◎ Dimensions: diameter: 100mm, high: 45mm (without base)
● BT-KVA001 coding combustible roof home
BT-KVA001, BR-KVA001, BT-VA001, BR-VA001 coding combustible roof household use semiconductor gas sensor, stable, simple installation, this type of alarm using DC24V centralized power supply, and the various fire alarm controller coordinated application. For your home, hotel, apartment and other places where flammable gases exist for security monitoring. BT-KVA001, BR-KVA001 two products provide for the control of ventilation equipment for passive normally open contact and control of the gas pipelines of the solenoid valve is the contacts of the source. BT-VA001, BR-VA001 two products only provide control of the gas pipelines of the solenoid valve is the contacts of the source. BT-KVA001, BT-VA001 applies to detect natural gas, BR-KVA001, BR-VA001 applies to probe manufactured gas.
The main technical indicators are as follows:
◎ Detection components: the natural diffusion-type semiconductors
¡Ã– power supply voltage: DC16V ~ DC30V
◎ Working current: monitoring current ≤ 80mA alarm current ≤ 100mA
◎ Alarm concentration: natural gas 5500ppm gas 1200ppm (H2)
◎ Warm-up time: 5 minutes
◎ Alarm: red LED flashes, accompanied by intermittent beeps
◎ Output contact:
Passive normally open contacts, capacity: 220V/3A,-only BT-KVA001, BR-KVA001
Active contacts, 0V ~ 12V one-way DC pulsed electromagnetic valve, drive capability: 2200 μ F/12 V capacitor discharge
◎ Using environment: temperature: 0 ° c ~ + 50 ° c humidity: ¡Ã¼95%Without condensation
◎ Dimensions: diameter: 137mm, high: 46mm (without base)
● BT-KVA002 coding combustible wall-mounted home
Encoding-mounted domestic combustible gas alarm using semiconductor gas sensor, stable, simple installation. This type of alarm using DC24V centralized power supply, and the Hudson Bay Company production of fire alarm controller to promise of second bus way to connect, and other types of fire detectors together to form a bus system, fire alarm system. Suitable for families, hotels, apartments and other places where flammable gases exist for security monitoring. There are two sound and light alarm status: general alarm and emergency alarm.
The main technical indicators are as follows:
◎ Detection components: the natural diffusion-type semiconductors
¡Ã– power supply voltage: DC16V ~ DC30V
◎ Working current: monitoring current 80mA, alarm current 100mA
◎ Alarm concentration: gas (BT-Y002 series)
Level alarm: 10000ppm 7000ppm secondary alarm:
◎ Warm-up time: 5 minutes
◎ Alarm: red LED flashes, accompanied by intermittent beeps. The general alarm, the red LED flashing frequency about 1Hz; emergency alert, red LED flashing frequency about 3Hz
◎ Output contact:
Passive normally open contacts, capacity: 220V/3A, only BT (R/Y)-KVA002 series
Active contacts, one-way 12V DC pulse electromagnetic valve, drive capability: 2200F/12V capacitor discharge
◎ Using environment: temperature: 0 ° c ~ + 50¡Ã¦ £ ¬2 relative humidity: 95%, no condensation
◎ Encoding: decimal electronic coding
◎ Dimensions: 176mm×80mm×45mm
● JTY-HS-G2-smart style infrared beam smoke detector
JTY-HS-G2-smart style infrared beam smoke detector built-in single-chip computer, have strong analytical judgment, by operation of the internal curing detectors may be auto-completion on the outside environment parameters change compensation and fire, failure of judgment and improves overall system detection accuracy of real-time and fire. The probes for use with the controller, you can fire alarm control system comprising, in particular, apply to the high-rise buildings, heritage protection construction facilities, Hall Museum, the warehouse group and tunnel project, where there is smoke in front of the fire formation of sites may use this product.
The probes debugging method is simple, debugging, use the fire light and fault lamp combination confirmation (on or off), and the controller of the ' fixed debug ' feature, you can continuously monitor the receiver light intensity trends for detector is debug, fix a non-intelligent infrared beam detectors for high-altitude on debugging difficult problems and job security.
The main technical indicators are as follows:
◎ Working voltage: transmitter: DC24V receiver: bus 24V
◎ Sink: monitor current ≤ 1.8mA, alarm current ≤ 2.5mA
Transmitter: monitor current ≤ 2.5mA (connected with 24V power supply, no polarity)
◎ Alarm acknowledgement lamp: Red fault led: yellow
◎ Using environment: temperature:-10 ℃ ~ + 50¡Ã¦ £ ¬2 relative humidity: 95%, no condensation
◎ Encoding: decimal electronic coding
◎ Dimensions: diameter: 100mm, high: 94mm (without base)
◎ Protected area:
This probe can be effective protection of a rectangular area, the largest protected area: 100m×14m
Friday, February 10, 2012
【 Weak current College 】 Gulf equipment technical characteristics and parameters (4)---Power By 【 China power house network 】
● JTW-LDB-100 type intelligent cable type heat detector
Smart cable type linear heat detector is JTW-LDB-100 type intelligent cable type linear heat detector coding interface, JTW-LDZ-100 type of Terminal and linear temperature sensor cable. This detector is the cable type heat detector, applicable to cable was in power and control cable fire early warning and control, power plants, steel mills, chemical plant, ancient buildings etc.
JTW-LDB-100 coding interface built-in single-chip computers that use electronic coding, line type heat detector access fire quotation system signal 2 bus. The first temperature sensor cable-end coding interface connection, end the connection with JTW-LDZ-100 type of Terminal. Each interface can connect two road temperature sensor cable, each occupying a code point.
Terminal for cable-linear heat detector private attachments, to the whole of the end of the temperature sensor cable without the need for access for fire alarm controller. Terminal with a temperature sensor cable fire test switch, easy to engineering simulation test pattern when debugging heat detector of alarm properties.
The main technical indicators are as follows:
◎ Operating voltage: 24V bus
◎ Monitor current ≤ 3mA
◎ Alarm current: 5mA
◎ Wire: interface and fire alarm controller with nonpolarized second bus connection terminal directly with linear temperature sensor cable connection
◎ Using environment: temperature:-10 ℃ ~ + 50¡Ã¦ £ ¬2 relative humidity: 95%, no condensation
◎ Dimensions: coding interface: Terminal: 120mm×80mm×40mm 162mm×200mm×80mm
● JTG-ZW-G1 type intelligent UV flame detector
UV flame detector by detecting material combustion produces ultraviolet to detect fires, apply to the fire occurred, easy to produce the open fire place, on the fires have strong flame or not smoldering stage places can be used this detector. The detector used in conjunction with other detectors, the timely discovery of fire, reduce losses.
UV flame detector sensor by use of imported components from UV-tube, with quick, reliable and resistant to dust, humidity and corrosive gases, etc.
The main technical indicators are as follows:
◎ Operating voltage: 24V bus
◎ Monitor current ≤ 2mA
◎ Alarm current: 10mA
◎ Wire: polarity signal 2 bus
◎ The detection angle ≤ 800
◎ Protection area: S = (h × t g α) 2 Ï€ (h: height from the ground, the detector α = 400)
◎ Alarm acknowledgement lamp: Red flashes when the inspection, the alert always lit
◎ Using environment: temperature:-20 ℃ ~ + 50 ° c relative humidity ≤ 95%, no condensation
◎ Dimensions: diameter: 100mm, high: 41mm (without base)
● JTF-GOM-GST601 type intelligent gas temperature composite probes
Compound detection technology is the internationally popular new multi-function high reliability of fire detection technology. JTF-GOM-GST601-flue gas temperature composite detector is my latest launch of a new detector, smoke sensors and semiconductor temperature sensors from process structure and circuit structure comprise of multiple complex detectors. It not only has intelligent photoelectric smoke detector performance, but also have fixed temperature, differential fixed temperature heat detector performance. It is precisely because of the smoke and heat of composite technology, makes this complex probes has overcome the normal forward scattering type photoelectric smoke detector smoke particles are not sensitive characteristics of smoke, to national standards test fire SH3 (polyurethane plastic fire) and SH4 (heptane fire) detection and alarm. At the same time that composite detector could also have significant alcohol burning temperature of fire detection and alarm, expanding the application of photoelectric smoke detector.
This detector is the promise of signal b bus system, you can access the Hudson Bay Company production of various types of fire alarm controller alarm bus. But these detectors with the Hudson Bay Company production of other probes are fully compatible, can be mixed on the same bus.
The main technical indicators are as follows:
◎ Operating voltage: 24V bus
◎ Monitor current ≤ 0.8mA
◎ Alarm current ≤ 2mA
◎ Alarm acknowledgement lamp: Red flashes when the inspection, the alert always bright, failure is off
◎ Fixed temperature alarm temperature: 90 ℃ (available through electronic encoder highest setting to 78 ° c)
◎ Using environment: temperature:-10 ℃ ~ + 50 ° c relative humidity ≤ 95%, no condensation
◎ Encoding: decimal electronic coding
◎ Dimensions: diameter: 100mm, high: 42mm (without base)
● JTGB-ZM-GST501/I/I-type flameproof UV flame detector
JTGB-ZM-GST501/I flameproof UV flame detector by detecting material combustion produces ultraviolet to detect fires, apply to the fire occurred, easy to produce the open fire place, and the other detectors, more timely detection of fire and minimize losses. JTGB-ZM-GST501/I flameproof UV flame detector for encoding flameproof products, explosion-proof performance conforms to GB3836.1-83 the explosive environment with explosion-proof electrical equipment-General requirements and GB3836.2-83 the explosive environment with explosion-proof electrical equipment flameproof electrical equipment "d" standard requirements while meeting GB12791-91 points-UV flame detector technical requirements and test methods "in the various requirements.
This detector explosion-proof type is suitable for explosion-proof ExdIICT6 zone 1 and zone 2 places various explosion-proof, according to the scene environment. Sensor made of imported products with high sensitivity, long life, reliable, etc. The detector used electronic encoding, available through our electronic encoder for encoding, encoding in the range of 1-242Room.
The main technical parameters are as follows:
◎ Operating voltage: 24V bus
◎ Monitor current ≤ 2mA, alarm current: 10mA
◎ Wire:-polarity and two-wire
◎ The detection angle ≤ 80
◎ Protection area: S (h * tg) 2 (h: detector is apart from the ground level, 40)
◎ Explosion-proof mark: ExdIICT6
◎ Using environment: temperature:-20 ℃ ~ + 40 ° c relative humidity ≤ 95%, no condensation
(3) alarm button
● J-SAP-8401-manual fire alarm button
J-SAP-8401 type intelligent coding manual alarm button design using innovative shape structure, recoverable characteristics, very suitable for application. Manual alarm button installed in public places, when artificial confirmed fire press the button on the plexiglass plate to the controller issued a fire alarm signal controller receives the alarm signal, displays the alarm button number or location and a beep sound. Manual alarm button directly on the receiving controller bus.
J-SAP-8401 type intelligent coding manual alarm button has the following characteristics:
(1) Manual alarm button uses the promise of signal b bus, its address coding by handheld electronic encoder in 1 ~ 242 between arbitrary.
(2) Manual alarm button uses the pluggable type structure design, button presses on the plexiglass film press reset after special tools available.
(3) press the alarm button glass, can be used by buttons provide rated DC60V/100mA passive output contact signal, can directly control the other external devices.
Manual alarm button uses the entire seal design, seams designed the gasket, with waterproof function. In addition, the Board adopts the waterproofing process, the surface of a waterproof plastic to protect the hand button on the inside of the moisture-proof performance.
The main technical indicators are as follows:
◎ Operating voltage: 24V bus
◎ Monitor current ≤ 0.8mA
◎ Action current ≤ 2mA
◎ Wire: and controller-polarity signal second bus connection
◎ Using environment: temperature:-10 ℃ ~ + 50¡Ã¦ £ ¬2 relative humidity: 95%, no condensation
◎ Dimensions: 90mm×122mm×48.5mm
● J-SAP-8402-manual fire alarm button (with the phone jack)
J-SAP-8402 intelligent coding manual alarm button (with the phone jack) design using innovative shape structure, recoverable characteristics, very suitable for application.
This manual alarm button electronic encoding, once confirmation beep, immediately signals to the controller, warning prompt. Manual alarm button located on the phone jack, when handheld phone after inserting the call should be made with the control center.
Manual alarm button uses the entire seal design, seams designed the gasket, with waterproof function. In addition, the Board adopts the waterproofing process, the surface of a waterproof plastic to protect the hand button on the inside of the moisture-proof performance.
The main technical indicators are as follows:
◎ Operating voltage: 24V bus
◎ Monitor current ≤ 0.8mA
◎ Action current ≤ 2mA
◎ Wire: and controller uses the promise of signal b bus connection and bus system coding telephone jack connection using four-wire, and multiple line telephone TS-Z02 hosts connections using phone II bus
◎ Using environment: temperature:-10 ℃ ~ + 50¡Ã¦ £ ¬2 relative humidity: 95%, no condensation
◎ Dimensions: 90mm×122mm×48.5mm
● LD-8403 type intelligent encoding fire hydrant alarm button
LD-8403 type intelligent fire hydrant alarm button for encoding type, you can directly access controller bus, representing an address encoding.
Button face a plexiglass plate, when enabled, fire hydrant, can be directly pressed glass, where the red light on the button, indicating that the control room to the fire alarm information was issued, the controller confirmed the fire pump has started running, to issue a fire hydrant alarm button command signal light pump operation indicator. Fire hydrant alarm button of pump operation led to the controller, also attracted by the pump control box direct pump running switch signal lights, according to the specific design requirements.
Alarm button uses the pluggable type structure design, button presses on the plexiglass film press reset after special tools available.
Alarm button electronic coding that uses the entire seal design, seams designed the gasket, with waterproof function. In addition, the Board adopts the waterproofing process, the surface of a waterproof glue, guarantee the performance of moisture inside the button.
The main technical indicators are as follows:
◎ Operating voltage: 24V bus
◎ Monitor current ≤ 0.8mA
◎ Alarm current ≤ 2mA
◎ Wire: fire hydrant alarm button signal with the controller, the second bus connections if you need to achieve direct cycle pump control and pump control box action lit pump running lights, fire hydrant and alarm buttons and pump control box are three bus connection
◎ Action led:
Red: the alarm button is pressed the lights green: the fire pump starts this lights
◎ Actions-contact: passive normally open contacts, with a capacity of DC60V, 0.1A, can be used to direct cycle pump control
◎ Using environment: temperature:-10 ℃ ~ + 50¡Ã¦ £ ¬2 relative humidity: 95%, no condensation
◎ Dimensions: 90mm×122mm×48.5mm
Wednesday, February 8, 2012
【 Weak current College 】 Gulf equipment technical characteristics and parameters (6)
● LD-8313-bus isolator
When the bus fails, the failure of bus parts and isolate an entire system to ensure that the system of the normal work of the other part, to determine the failure of bus parts. When the failed part of the bus after repair, bus isolators can resume work, will be separated out part into the system, maintenance is simple. LD-8313-bus isolator based on actual number set by the next detector with load capacity of their own, bus isolator with 170mA and 270mA two current, direct-line on the bus, using flexible.
The main technical indicators are as follows:
◎ Operating voltage: 24V bus
◎ Action current: 170mA (maximum access 50 coding equipment); 270mA (maximum access 100 encoding device)
◎ Quarantine actions confirm lamp: Red
◎ Using environment: temperature:-10 ℃ ~ + 50¡Ã¦ £ ¬2 relative humidity: 95%, no condensation
◎ Dimensions: 120mm×80mm×39mm
● LD-8319 coding repeaters
LD-8319 coding Repeater is a code module that is used to connect non-encoding detector, occupies only one code point, when the access code relays output circuit of any field device alarm, the alarm relays information to the alarm controller, controller generate alarm signals and display the address of a Repeater. Repeaters can be with the company's production of JTFB-GOF-GST601 noncoding flue gas temperature composite detector, JTY-GF-GST104 noncoding photoelectric smoke detector and JTWB-ZCD-G1 (A) non-encoded electronic differential fixed temperature heat detector, etc. Repeater with output circuit breaker test function, output circuit terminal connection active Terminal LD-8320, when output circuit breaker, coding repeaters will fault information to alert the controller, the controller displays the encoding of the repeaters; when the output circuit with on-site equipment is removed, the encoding will report a failure but a Repeater does not affect the other field devices work correctly. A Repeater can bring many non-encoding detector, you can also mix multiple detectors, but mix the quantity not exceeding 15 only.
Repeaters using four-wire system, the controller needs two alarm signal bus (polarity) and two dc24v (polarity), encoding the relays output polarity with probes used a two-wire connection.
Repeater address coding using electronic encoding encoding range 1 ~ 240 set between, the Hudson Bay Company production of BMQ-1 type electronic encoder for scene changes.
LD-8319 coding repeaters and non-encoding detector series connection, the detector base should add diode 1N5819, and output circuit terminal must add LD-8320 active Terminal. A source terminal can be used when the detector base, that is, the source terminal can be installed non-encoding detector. When a source Terminal is not used as a detector base, should be loaded on the cover. The engineering equipment configuration in order to reduce costs, using Active terminal when the detector base used in active Terminal directly installed non-encoding detector installation mode that reduces the number of the detector base.
The main technical indicators are as follows:
◎ Operating voltage: 24V voltage bus: bus, power supply voltage: DC24V
◎ Monitor current ≤ 0.5mA
◎ Alarm current: 5mA
◎ Wire: and controller uses the promise of signal b bus connection and power supply cord with promise of two-wire connection, and non-encoding detector using polarized two-wire connection
◎ Using environment: temperature:-10 ℃ ~ + 50¡Ã¦ £ ¬2 relative humidity: 95%, no condensation
◎ Dimensions: 120mm×80mm×40mm
● LD-8320 active Terminal
In non-coding automatic fire alarm system, the traditional way is through the circuit terminal connection a resistance to maintain the system's normal work, once the entire matching undue alarm system is not functioning, or even produce a false alarm. LD-8320 active Terminal and supporting the use of LD-8319 coding repeaters to replace terminal resistor, when the alarm system output circuit with on-site equipment is removed, the Repeater to LD-8319 coding controllers report fails, but does not affect the other field devices work correctly. Effectively solved the above problem, greatly improving non-coded alarm system reliability.
The main technical indicators are as follows:
◎ Working voltage: DC15V ~ DC28V
◎ Nominal voltage: DC24V
◎ Equivalent resistance: 4.7 k Ω
◎ Using environment: temperature:-10 ℃ ~ + 50¡Ã¦ £ ¬2 relative humidity: 95%, no condensation
◎ Dimensions: diameter: 103mm, high: 38mm
(5) fire show up
● ZF-101 fire show up
ZF-101 fire show up is a single-chip design and development can be installed on the floor or independent zones digital fire alarm display device. By bus and fire alarm controller, handling and display controller transfer over the data. When building a fire, the fire control centre of the fire alarm controller generate alarm, alarm signal is transmitted to the fire area fire shows up. Displays the disc will result in a fire alarm detectors numbers and related information is displayed, and produces sound and light alarm signal, to notify the fire zone. Fire show up with 8-bit alarming information display window, you can set alarm detector code number shown to meet a wide range of alarm display requirements. When using a single alarm controller while monitoring several floors or fire partitions, each partition set floors or fire fire shows up in place of the area alarm controller.
The main technical indicators are as follows:
◎ Display range: display range: 00000000 ~ 99999999 in arbitraryAlarm code points
◎ Shows capacity: up to 50 of alarm information
◎ Wire: and fire alarm controller using a polarity second bus connections to two DC24V power supply cable (no polarity)
◎ Using environment: temperature: 0 ° c ~ + 40 ° c humidity: ≤ 95%, no condensation
◎ Power: DC16.8V ~ DC26.4V power centralized power supply
¡Ã’ saving state power consumption ≤ 1W, maximum power consumption ≤ 2W
◎ Dimensions: 230mm×142mm×70.5mm
● ZF-500 type Chinese character LCD display tray fire
ZF-500 fire displays disc is single-chip design and development of kanji-fire show up to show the fire detectors part number and character information and at the same time issued a sound and light alarm signal, the display is clear and intuitive, easy to confirm. By bus and fire alarm controller, handling and display controller transfer over the data. When an alarm while monitoring several floors or fire partitions, each partition set floors or fire fire shows up in place of the area alarm controller.
The main technical indicators are as follows:
◎ Display range: each screen displays 4 alarm information, subsequent alarm information can cycle through the
◎ Shows capacity: up to 126 alarm information
◎ Wire: and fire alarm controller using a polarity second bus connections to two DC24V power supply cable (no polarity)
◎ Using environment: temperature: 0 ° c ~ + 40 ° c humidity: ≤ 95%, no condensation
◎ Power: DC16.8V ~ DC26.4V power centralized power supply
¡Ã’ saving state power consumption ≤ 2W, 3W max power consumption ≤
◎ Dimensions: 230mm×142mm×70.5mm
● ZF-GST8903-graphical fire show up
Fire show up is ZF-GST8903 a floor of fire alarm display device. When the fire control centre of the host receives a building after fire, alarm, the alarm signal is transmitted to the fire area fire shows up, fire show disk will produce an alert detector location displayed and a beep sound to notify the fire zone.
This shows up for non-standard products, according to the project actual requirements and under fire shows up the displayed alarm zone layout customization.
The main technical indicators are as follows:
◎ Display range: 1 ~ 64 encoding.
◎ Shows capacity: up to 64 alarm message.
◎ Wire: and fire alarm controller using a polarity second bus connections to two DC24V power supply cable (no polarity).
◎ Using environment: temperature: 0 ° c ~ + 40 ° c humidity: ¡Ã¼95% (40 ° c, 2 ° c)
¡Ã– power supply: DC24V power centralized power supply, power dissipation ≤ 1W
◎ Dimensions: 345mm×235mm×70mm
(6) power
Monday, February 6, 2012
【 Weak current College 】 Gulf equipment technical characteristics and parameters (7)---Power By 【 China power house network 】
● GST-DY-100-type power supply box
GST-DY-100-power box is a DC24V bulk power output equipment, fire alarm control system that can be used as a coordinated control system of power, as linkage control module and charged device power supply. Power supply unit to the AC 220V as main power, while the built-in DC24V/7Ah sealed lead batteries as backup power supply, switching power supply voltage circuits and maintain electrical floating charge, with output over-current protection, and standby power switch and the perfect preparation of electric power by automatically charging and over-discharge protection. At the same time, the intelligent power supply unit can be kept on the main, electrical and power output status monitoring, master, power failure, fault output, but also has an output voltage, output current display feature to visually observe power box working state.
The main technical indicators are as follows:
◎ Rated output capacity: DC24V, 4A
◎ Using environment: temperature: 0 ° c ~ + 40 ° c relative humidity ≤ 95%, no condensation
¡Ã’ main power for power: AC 220V, built-in DC24V7Ah sealed lead batteries be electro
◎ Dimensions: 310mm×400mm×115mm
● GST-DY-200-smart power box
GST-DY-200-smart power box is a DC24V bulk power output equipment, fire alarm control system that can be used as a coordinated control system of power, as linkage control module and charged device power supply. Power supply unit to the AC 220V as main power, while the built-in DC24V/24Ah sealed lead batteries as backup power supply, switching power supply voltage circuits and maintain electrical floating charge, with output over-current protection, and standby power switch and perfect automatic charging and prepared by electric over discharge protection. At the same time, the intelligent power supply unit can be kept on the main, electrical and power output status monitoring. When the input voltage is greater than or less than 260V 160V times main power failure; when preparing electrical battery damaged or undervoltage electrical fault when filing; when the output voltage is greater than the 28V or output current greater than 8A times output fault. The power box also has a main electrical voltage, output voltage, output current display feature to visually observe power box working state.
The main technical indicators are as follows:
◎ Rated output capacity: DC24V, 6A
◎ Using environment: temperature: 0 ° c ~ + 40 ° c relative humidity ≤ 95%, no condensation
¡Ã’ main power for power: AC 220V, built-in DC24V24Ah sealed lead batteries be electro
◎ Dimensions: 500mm×440mm×170mm
● GST-LD-D02-intelligent power-up
GST-LD-D02-intelligent power disk circuit by AC-DC conversion, standby power float control circuit and power control circuit is composed of three parts, specifically for the entire fire control system power supply.
GST-LD-D02-intelligent power up to AC 220V as main power, while the external battery DC24V/24Ah as preparation. Standby power normally accept main power charging, when the site AC power failure, the standby power supply automatically import external supply. Intelligent power supply tray can be on the main electrical faults and alarm output failure, when the input voltage is greater than or less than 160V 260V, reported main power failure; when the output voltage is greater than the 28V or output current greater than 8A, report output. At the same time it also has a battery overcharge and over discharge protection. Power monitor parts for indicating that what is currently being used by all the way to the power supply, AC input voltage and output voltage values, as well as various fault and status display. In a tank fire alarm controller (linkage) as the control core systems, the power-up as a coordinated control system power.
The main technical indicators are as follows:
◎ Output capacity: DC24V, 6A
◎ Using environment: temperature: 0 ° c ~ + 40 ° c humidity: ≤ 95%, no condensation
¡Ã’ main power for power: AC 220V, built-in DC24V24Ah sealed lead batteries be electro
(VII) fire broadcasting system
• Bus system fire emergency broadcasting system
Fire emergency broadcasting system belongs to the fire alarm control system supporting the use of equipment, through this system you can achieve communication building fire, command related layer evacuation capabilities throughout the fire control system plays an extremely important role.
Bus system fire emergency broadcasting system by the Hudson Bay Company production of fire control centre of the broadcast equipment, with the use of the bus system for fire alarm controller, LD-8305 fire radio module and playback devices. The fire control centre of the broadcast equipment including radio power amplifier, CD recording disc GST-CD type and GST-KZ-deck recording disk, you can set in the Cabinet. Live broadcast using roof and wall-mounted speakers. Use fire radio switch module LD-8305, scene playback device on the bus access controllers, sent by the radio device to the audio broadcast signals, but also through LD-8305 module passive normally open contact (fire broadcasting) and normally closed contact (normal broadcast) added to the playback device, a radio range may be a LD-8305 module to control. The module is equipped with auto-answer feature, when the module actions will generate an alarm signal is fed into the controller generates alerts indicating that normal broadcast and fire broadcasting switch successfully.
Fire emergency broadcasting system playback device can be private or share with the public broadcasting system; when combined with the public broadcasting system, the fire control centre must be fire evacuation level for the speakers and to public broadcasting amplifiers force fire emergency broadcast status while in the fire control centre monitors fire emergency radio amplifiers working state.
Fire broadcasting equipment together with other devices can also be individually assembled in fire control cabinets, equipment power unity by fire control system of power supply.
«More wire fire emergency broadcasting system
Fire emergency broadcasting system belongs to the fire alarm control systemCommission in supporting the use of equipment, through this system you can achieve communication building fire, command related layer evacuation capabilities throughout the fire control system plays an extremely important role.
More wire fire emergency broadcasting system by the Hudson Bay Company production of fire control centre of the broadcast equipment, fire alarm controller, LD-GBFP-100 multiple wire broadcast distribution and live broadcast speaker. The fire control centre of the broadcast equipment including radio power amplifier, CD recording disc GST-CD type and GST-KZ-deck recording disk, you can set in the Cabinet. Live broadcast using roof and wall-mounted speakers. More wire fire broadcasting system's output of broadcasting channels by broadcasting Division to design, each broadcasting a second root partition independent broadcasting channels and live playback devices are connected, the broadcast Division switching control by the fire control centre dedicated multi wire fire broadcast distribution (LD-GBFP-100 type). With this switch, you can complete manually on the broadcasting Division for normal or fire radio switch.
Fire emergency broadcasting system playback device can be private or share with the public broadcasting system; when combined with the public broadcasting system, the fire control centre must be fire evacuation level for the speakers and to public broadcasting amplifiers force fire emergency broadcast status while in the fire control centre monitors fire emergency radio amplifiers working state.
Fire broadcasting equipment together with other devices can also be individually assembled in fire control cabinets, equipment power unity by fire control system of power supply.
(8) fire telephone system
• Bus system fire telephone system
Fire telephone system is a dedicated communication systems for fire, this system can quickly achieve the fire of artificial confirmation, and may hold the fire site and carry out other necessary communications, to direct the fire suppression and recovery work. Telephone system host installation in the control center, the use of embedded installed in the alarm control stringed Cabinet.
The complete bus system fire telephone system consists of a set of fire control centre GST-TS-Z01A-bus system fire phone host and fire alarm controller, on-site LD-8304 module and LD-8312-phone jack and TS-100A fire telephone extension. The system has a design flexible, easy to use and so on.
GST-TS-Z01A-host with recording function, using digital voice memory chips up to record a 30-minute call to fire accident investigation.
LD-8304 module is a direct encoding module, and the fire alarm controller bus connection and need to be connected to the power bus DC24V. To achieve the delivery of telephone voice signal, you need to access the fire phone bus. LD-8304-module has a telephone jack, you can direct telephone extension for bus system.
LD-8312-phone jack and J-SAP-8402 type intelligent coding manual alarm button telephone jack parts are non-coding, direct bus connections with fire telephone constitute non-coded telephone jack, if-module connection with LD-8304, may constitute a coding style phone jack.
Fire telephone system telephone extension can call host without dialing, ringing when the host is the call until the host off-hook or extension to cancel the call; at the same time, the host may call any fixed extension (by fire alarm controller), the extension is ringing when the call until the extension off-hook or cancel the call of fire alarm controller; extension between host allows also can call; telephone jacks can be expanded. Pick a fixed telephone extension or extension plugged LD-8312-Jack and J-SAP-8402-Manual alarm button (including telephone socket) phone jacks are considered extensions caller host. The host calls fixed extension can fire alarm controller starts the appropriate LD-8304 modules allow extension ring. Host and extension, extensions and extension of the call, the call is completed by the host's own control without the need for other controllers.
«More wire fire telephone system
Fire telephone system is a dedicated communication systems for fire, this system can quickly achieve the fire of artificial confirmation, and may hold the fire site and carry out other necessary communications, to direct the fire suppression and recovery work. Telephone system host installation in the control center, the use of embedded installed in the alarm control stringed Cabinet.
Complete wire fire telephone system consists of a set of fire control centre TS-Z02A-multi wire fire phone host and fire alarm controller, LD-8312-phone jack and TS-200A stationary fire telephone extension and TS-200B hand-held fire telephone extension. The system has a design flexible, easy to use and so on.
More wire fire telephone system control core for multiple-line TS-Z02A-fire phone hosts. According to the actual demand, fire phone hosts capacity is not the same. Fire in a multiple-line telephone system, each Department TS-200A type fixed fire Ext. occupy all the way to fire phone hosts, separate two-wire and fire phone hosts connections. LD-8312-fire phone jack can be connected in parallel, parallel, or as many as you like, parallel telephone jack fire phone only occupies one of the host.
Fire telephone system telephone extension can call host without dialing, ringing when the host is the call until the host off-hook or extension to cancel the call; at the same time, the host may call any fixed extension (by fire alarm controller), the extension is ringing when the call until the extension off-hook or cancel the call of fire alarm controller; extension between host allows also can call; telephone jacks can be expanded. Pick a fixed telephone extension or extension plugged LD-8312-type jacks are considered extensions caller host.
More wire fire telephone system host and extension, extensions and extension of the call, the call is completed by the host's own control without the need for other controllers.
(9) gas extinguishing control
● LD-QKP06 type gas fire extinguishing Control Panel
LD-QKP06 gas extinguishing Control Panel is a project of the actual requirements of gas fire extinguishing control interface device, used to drive a gas fire extinguishing system of executive bodies, so as to constitute a complete gas fire control system. This control panel you can directly access fire alarm controller bus, and the company's production of linkage controller or fire alarm controller together with the completion of the gas cylinders, automatic control to control fire extinguishing gas spray.
The control panel can be independent of the linkage controller or fire alarm controller on the connected external device control. The fire alarm controller when an exception occurs, through on-site emergency start/stop-button or the gas fire extinguishing Control Panel on start and stop moving directly to the key realization on gas fire extinguishing equipment of control actions.
LD-QKP06 gas extinguishing Control Panel can be attached spraying led, emergency boot/shutdown action buttons, independent control linkage more wire devices. Extinguishing control panel with external line short circuit and open circuit check alarm function, and have an alternate number line output to ensure that the main gas fire extinguishing equipment maintenance or failure to use an alternate control output reached gas extinguishing purposes.
The main technical indicators are as follows:
◎ Capacity: maximum capacity of control 6 gas fire district (six control unit)
◎ 0s---45s adjustable delay time:
◎ Wire:
A. controller uses two bus connection (polarity signal second bus)
B. steel solenoid valve, pressure switch and spray led multiple wire 2-wire connection
C. emergency boot/shutdown dynamic buttons using multiple wire 3-wire connection
D. xiangqi with sound and light; adopts 2-wire connection
E. exterior with nonpolarized DC24V power
◎ Output: the output tray has 6 points, each group has two DC24V output (main and standby fire)
◎ Using environment: temperature: 0 ° c ~ + 40 ° c relative humidity ≤ 95%, no condensation
◎ Power: DC24V6V (for), you can connect with intelligent power-up or intelligent power box
◎ Monitor power consumption ≤ 10W
◎ Dimensions: 460mm270mm105mm
Sunday, February 5, 2012
【 Weak current College 】 fire engineering installation technology gives the low-down-Power By 【 China power house network 】
Technology gives the low-down the records table C2-1 number, project name gives the low-down on the construction unit sub-item project name to give the low-down the feeds low-down: fire engineering installation of universal scope 1 this craft standard applicable to industrial and civil building fire equipment installation engineering. 2 construction preparation 2.1 construction design of fire design drawings, you must have the appropriate design qualification certificate of design unit design. The construction drawings and information will be sent to public security and fire fighting supervisory body audit, approved by the audit. 2.2 engaged in fire-fighting facilities construction units, should have the appropriate qualification, their qualification by the public security fire agencies with the relevant departments to jointly approved and issued a fire protection engineering construction Enterprise qualification certificate. 2.3 construction field of fire safety by the construction of the units responsible. Pre-construction and construction units must be reported to the police and fire agencies, the public security agency issuance of permits for the construction site before construction of fire safety. 2.4 construction units must be in accordance with the approved design drawings, not tampered with. 2.5 installed fire products, mechanical and electrical products and materials to meet the following criteria: version 2.5.1 of the city of fire Eagle, should have a production license issued by the State. Foreign or foreign to local sales of fire protection products, must have a validity period of the sales control certificate in Beijing. Selection to the Tribunal that the products listed in the certificate is in line with the desired product. 2.5.2 fixed fire extinguishing systems and fire-resistant components and refractory coatings should have effective national quality inspection center of inspection reports. 2.5.3 fire electronic products to have a valid national fire electronic products quality inspection report. 2.5.4 selection of high-voltage Cabinet and cage screen must follow the machinery Department and Ministry-approved designated plant production products; import of electrical products must have a verification certificate, they have a certificate that the device has a nameplate. 2.5.5 construction electrical construction-to-use products such as wire and cable, switches, etc., should be consistent with the safety of China electrical Certification Committee, its certification requirements for electrical product safety certification Committee on should a security certification requirements, its electrical product safety certification mark shall carry, and has a certificate that has a nameplate on your device. 2.5.6 selection of various types of steel, shall meet the relevant standards and design requirements, manufacturers to produce material certificates and certificate. 2.5.7 various main accessories, pipes, welding rods, paint, etc., should have the certificate of quality. Selection of the machines must 2.6 meets the technical requirements of the construction site, the use of mandatory testing and non-mandatory testing of the measuring instrument shall be adjusted according to the national measurement Act at the request of management. 2.7 construction management personnel, such as construction, quality inspector, materials such as operationalizing certificates. Special types, such as electricians, welders, etc. should also be done certificates. 2.8 construction should accept firefighting supervisory authority and quality supervision authorities and other superior unit check instructions to ensure the quality of the project. 2.9 construction should be strictly in accordance with the approved design drawings, conscientiously implement the relevant fire design specifications, construction approval standard, construction technology and related Atlas, manufacturer information, and other construction requirements. 2.10 construction records and data collection, arrangement and fill out the form, you should do and engineering, project completion and acceptance of delivery time should be directed to the construction of a complete set of project information, and in accordance with the contract requirements, draw the as-built drawings. 2.11 fire engineering installation and debugging all completed, construction unit should be from a qualified surveyor, then please construction units (supervision), design units for acceptance, acceptance certificate of completion. 2.12 building units or construction unit should be entrusted to qualified building fire facilities detection unit tests and submit the technical test report. 2.13 construction unit should fire supervision agencies submit an application to and acceptance of the relevant information, the public security fire agencies, the fire engineering acceptance inspection issued to fire facilities only allow acceptance certificate, otherwise, the unqualified acceptance or non-acceptance shall be permitted to use. Person who accept to give the low-down the person gives the low-down
Thursday, February 2, 2012
【 Weak current College 】 mechanical smoke extraction facilities in fire acceptance of problem---Power By 【 China power house network 】
As China's economic construction fast development, high-rise buildings, underground works in some big cities like mushrooms and prospered. Modern high-rise buildings often makes extensive use of plastic decoration, the chemical fiber rug and furniture with foam padding. In the event of fire, Interior fuel and construction materials, decoration materials, flammable furniture, clothing and other combustible materials, such as in the combustion process produces a large amount of toxic smoke and heat, smoke does great harm to the human body, suffocating, poisoning still to death. According to a recent fire deaths statistics indicate that the fire deaths due to smoke smoked death accounted for about 50% to 70%, and burned to death in the majority of first asphyxia collapsed after burned to death. Construction of smoke control facilities in the fire for the safe evacuation and fire fighting created favorable conditions for, and control the fire from spreading. Therefore, the setting is very important for smoke control facilities. In order to design and install smoke control facilities, play, make sure that the State and people's lives and property. Author mechanical smoke extraction facilities in fire acceptance of several opinions on. For reference purposes only.
First, review the settings part of smoke control facility complies with the specifications
(A) mechanical smoke settings parts. Under the high civil building design fire protection standard section 8.3.1 bis provides for the following positions should set the mechanical pressurization smoke control facilities:
1, do not have conditions of natural smoke exhaust smoke fire stairs, elevator room or room before use;
2. adopt the measures of natural smoke exhaust smoke staircases, its does not have natural smoke conditions before the Chamber;
3, closed asylum bed (room).
(B) mechanical smoke extraction settings parts.
1, according to the design of tall building fire code provisions of section 8.4.1: a class of high-rise buildings and building height exceeding 32m II the following parts of high-rise building, you should set the mechanical smoke extraction facilities:
(1) no direct natural ventilation, and longer than the inner passages or 20m although direct natural ventilation, but longer than the inner passages 60m;
(2) more than 100m2, and often someone stay or fuel more ground and set the windowless room or room with a fixed window;
(3) does not have natural smoke conditions or headroom above the Atrium 12m;
(4) in addition to using window wells, and other fenestration for natural smoke rooms, each room has a total area of more than one room area 200m2 or exceed 50m2, and often someone stay or so of more basement.
2, according to the civil air defense air engineering design fire protection standard law, the following part shall be located mechanical smoke extraction facilities:
(1) building area greater than 50m2, and often someone stay or so in more rooms, lobby and c. "workshop;
(2) total length exceeds 20m evacuation aisle;
(3) film and stage.
3, according to the garage, garage, yard design fire protection standard stipulates: over 2000m2 of underground garage should set mechanical smoke extraction system.
(3) dance installstion smoke, smoke extraction facilities set parts. According to the architectural design fire protection standard article 5.1.1 and tall buildings design fire protection standard of 4.1.5A bis, these parts should be fortified to smoke, smoke extraction facilities:
(1) dance installstion located in multi-story building and including four stories above a windowless room or room-room window, underground rooms, as well as more than 20m and no natural smoke evacuation aisle or directly on the natural ventilation, but longer than 40m evacuation in aisle;
(2) dance installstion located in high-rise building of the first floor, second floor, the third layer, the area over the windowless room 100m2 or supposes a fixed window of the room and over 20m and no natural smoke evacuation aisle or directly on the natural ventilation, but longer than 60m evacuation in aisle;
(3) dance installstion located in high-rise buildings up to and including four stories above a windowless room or room-room window, underground rooms, open the window size is smaller than the room area of more than 2%, and with no natural 20m smoke evacuation aisle or directly on the natural ventilation, but longer than 60m evacuation in the aisle.
2. check the system settings for conformance to specifications
(A) of the pressurization system for smoke: 1, more than 32 storey high-rise building is segmentation settings ventilation system; 2, smoke staircases and combined with former rooms are separately set the air supply system, when you must share a system, whether on the way to the front room with air duct pressure difference set on automatic control device; 3, refuge layer is a separate ventilation system; 4, scissors staircase is set independently for the air duct, with the wind as second staircase; 5 ways to determine if the pressure to meet the requirements.
(B) mechanical smoke extraction system: 1, ground and underground is common exhaust system; and 2 whether the individual settings of the Atrium, the exhaust system; 3, mechanical ventilation and smoke extraction system, air-conditioning system and, when combined, whether or not to take the reliable security measures; 4, aisle and room exhaust system is set separately; 5, each exhaust system with exhaust port number is more than 30; 6, basement room is also equipped with air intake system (air mechanical air or natural) into the air should be not less than 50% of the exhaust gas volume and reasonable airflow should be organized so that the smooth discharge of flue gas.
3. view the fan selection is justified.
(A) the smoke pressurization system air supply available look-up or calculation method to determine when the calculated value and the tall buildings design fire protection standard of table 1, table 8.3.2-8.3.2-2, table 3, table 8.3.2-8.3.2-4 inconsistent, whichever the greater value. Then select according to the air or in axial flow fan and low-pressure centrifugal fan.
(B) mechanical smoke extraction system exhaust fan choice whether: 1, when the burden of an exhaust fan for smoke partition, you should press the smoke partition area per square meter than 60m2/h; 2.When the burden of two or more smoke partition should be maximum preventing smoke partition area per square meter than 120m2/h; 3, the volume is less than 17000m3 Atrium, the exhaust gas volume by volume of 6/h ventilation calculation; the Atrium volume greater than 17000m3, its exhaust volume according to the volume of the 4th/h ventilation; but most small amount should not be less than smoke 102000m3/h. According to the size of the calculated value, you can select the centrifugal fans, axial fans, smoke, or you can choose to bring the power of a dedicated exhaust fan.
4. view the air or exhaust port settings location is appropriate
(A) positive-pressure supply outlet: 1, smoke stairway supply outlet is every two to three-layer settings, former room air is layer sets; 2, each supply outlet area size meets the design requirements.
(B) mechanical exhaust outlet: 1, each smoke partition is at least one smoke exhaust vents; 2, smoke partition from the exhaust port within the furthest point of the horizontal distance is more than 30m; 3, exhaust port is located in the ceiling or wall near the ceiling; 4, each exhaust port area size meets the design requirements.
5. test smoke system feature is complete
(A) positive pressure ventilation system: 1, fan distribution meets the requirements, in the last level distribution box office is set up automatic switching devices; 2, fans in fire control room is one of the Start button, in the event of fire, pressure blowers can be started immediately; 3, supply outlet (except for opening pressure air) is set to manually, and automatic opening device, if there are any smoke detector chain of automatic opening device or fire control centre distance control of opening device; 4, smoke staircases, front room, shared room, fire before the elevator room, closed asylum bed (room) residual pressure value is reached the high civil building design fire protection standard article 8.3.7 bis regulations.
(B) mechanical smoke extraction system: 1, fan distribution meets the requirements, in the last level distribution box office is set up automatic switching devices; 2 whether the exhaust outlet, closed weekdays is set manually and automatic opening device, if there are any smoke detector chain of automatic opening device or fire control centre distance control of opening device; 3, in fire control room if there is a fan of one-to-one manual operation button;; 4, when any of the exhaust vents or exhaust valve is opened, the exhaust fan is able to boot; 5, in the exhaust pipes and exhaust fan room entrance is there when the gas temperature of more than 280 ° c, could itself off smoke fire dampers; 6, same smoke partition settings of exhaust port, can be opened simultaneously all exhaust port.
VI. other issues
1. smoke fan downlead of distribution lines with fire performance requirements;
2. air wind speed is not greater than 7m/s, the exhaust vents should not be greater than the wind speed 10m/s;
3, galvanized metal duct, the wind speed should not exceed 20m/s when using concrete block or asbestos Board other non-metallic materials, duct, the wind speed should not exceed 15m/s.
4, headroom than indoor Atrium 12m, vertical exhaust port is 2 to 3 layers of a smoke exhaust vents or segmentation settings;
5¡ ¢ exhaust fan is set in the exhaust system up to the upper part of the exhaust gas outlet does not use the upper to the lower deck of flue gas duct of the arrangement;
6. pressure blower is set free from building fire blower room, it is best to set on the bottom of the system, and the pressurization system of pipes should not be installed for fire dampers.
Wednesday, February 1, 2012
【 Weak current College 】 smoke control in high-rise building facilities design and construction analysis of and solutions to common problems
Summary: on the tall buildings of smoke control system design and construction issues analysis and countermeasure
Keywords: tall buildings, natural smoke exhaust system
Usually tall buildings of smoke control facilities include smoke staircase and vestibule, fire the elevator room, combined with front room, enclosed stairway, refuge layer (room), and other places set of smoke, the basement, in the aisle, Atrium, no form or with fixed window room and set the smoke extraction facilities, smoke partition between the vertical wall of smoke. Smoke management facilities is tall buildings to protect life and property safety indispensable fire safety facilities, but as part of the design and construction personnel on smoke control facilities of structure, function, performance, lack of awareness, understanding of national regulatory standards, not often leads to the design, construction, there are some problems, mainly in the following areas:
A, natural smoke extraction facilities up to exhaust purpose
Natural gas is an economical, simple and easy operation, maintenance, management convenience of exhaust smoke, but as part of the works in the design and construction process is not carried out according to specifications, often lead to project completion, natural smoke extraction facilities do not have the effect of its smoke causes mainly has following several aspects:
A is the set of natural smoke exhaust was misaligned window. From natural smoke effect, exhaust window should be as close as possible to the top of the wall, there are a considerable number of natural smoke exhaust window is set in the upper part of the wall, but is lower, from the roof, the greater the distance from the ceiling, is not conducive to natural gas.
Second, natural smoke exhaust window window area does not meet specifications. National standards for the design of tall building fire safety norms on the use of natural smoke exhaust parts of fenestration area shall be clearly defined, but due to some designers do not press specifications carefully calculated, or the fixed window area within the exhaust window area, causing some projects don't exhaust window area to the specification requires that directly affect the smoke effect.
The third is the natural structure of exhaust window. Have made the smoke exhaust window is not open, fixed window, the upper portion of the form to make a fixed window, the window can be opened by the smoke in the lower portion of the window, seriously affect the smoke extraction functionality.
4. installation height high exhaust window missing easy to open the operating organization. According to specification, exhaust window should have opened the device easily, but some of the installation height high, difficult exhaust window are not installed on the negative operating device, fire smoke exhaust window opens.
2. set the mechanical pressurization smoke control equipment parts required to form a top pressure value, mechanical smoke extraction facilities of smoke effect is not evident.
Air and exhaust air, port Yu ya value does not meet the regulatory requirements of the phenomenon is more prevalent in the project, some air, exhaust port speed or even close to zero, this might be caused by more complex, mainly has following several aspects:
1. improper fan selection. According to specification, smoke staircase and vestibule, combined with front room and fire the elevator room of mechanical pressurization air flow, the calculation should be identified, when the calculated values and norms stipulated values do not match, whichever the greater value determines the design directly, according to the specification for a given value determines that often lead to the selection of the blower air flow, pressure is small, can not meet the requirements of the design uses combined ventilation and smoke extraction system, construction was not as designed selection two-speed fan; construction units not complying with the design of the fan model ordering, purchasing power specifications smaller fan, led to a serious shortage of fan.
2. mechanical pressurization system and natural gas facilities in the repeat settings. For building height more than 50 meters of a class of public buildings and buildings of more than 100 meters of residential buildings, in accordance with the requirements of the regulations should set mechanical pressurization system, some projects in this area while using natural gas, resulting in fire, mechanical pressurization system for smoke control window with nature while opening, smoke stairs difficult to form a positive pressure, can not reach the smoke effect.
3, combined with the positive pressure ventilation system was not designed pressure regulation device. According to specification, mechanical pressurization for smoke control staircase and combined with former room, to independently set the air supply system, when you must share a system should be on the way to the front room with air duct pressure difference set on automatic control device. There are many design combined with the positive pressure ventilation system does not have design pressure regulation device, unable to form a staircase of residual pressure is higher than the front room.
4. smoke partition not complying with the specifications set smoke facilities. A considerable part of the project, especially the large shopping centres set up smoke part not specifications set down in the ceiling smoke vertical walls, basement while using architecture beam for smoke, smoke extraction system in the exhaust vent is not according to specification, located in the ceiling or wall near the ceiling, which is located below the beam.
5. air settings do not meet the requirements. Some vertical smoke control system for air fixed louvres-normally open air outlet, outlet sizes basically the same, caused by the layer of air volume and air speed serious imbalances, far away from the fan supply outlet of the air flow is inadequate, even at the end of the diffuser of wind speed, wind rate close to zero.
6, duct shaft construction, air quality is poor. A considerable number of works by ventilation shafts not plastering, plumbing connections are not closed position, normally closed air leakage is not tightly closed, causing very serious air, exhaust air flow of wind speed, the specification requirements, construction unit or even cancel the shaft connection ceiling diffusers for air pipe, use ceiling stuffy air duct space instead of a top, often causing air duct outlet wind speed close to zero.
While some will exhaust system fan exhaust port is set in the Interior, fire smoke from indoor Interior to not only lose the smoke effect, but also may cause the spread of fire.
3. smoke fan of distribution does not conform to specification
One is the fan's power supply to the load level of tall buildings. Some of the power supply line not received since the fire power, but rather add to floor lighting, power distribution box, some design uses single circuit distribution lines, design is not set at the end of the power supply automatic switching device, not a secondary power supply load requirements, exclusive dual-circuit, located at the end of the automatic switching device.
Second, the downlead distributionInstallation of electric lines does not meet the requirements. Some smoke fan distribution line wear PVC plastic pipe, some wear metal tube not brushing fire retardant coating, does not comply with the wearing of fire performance requirements.
4. setting up machinery parts of smoke control facilities specifications set by
1, with podium of smoke control in high-rise building stairwell and front room, fire the elevator room or shared room, when the podium above use can be opened for natural smoke outside Windows, podium section does not have natural smoke condition, its front room or room is not in accordance with the former specifications set positive pressure ventilation system.
2. no more than 20 meters of natural gas in the aisle, some designers who connected smoke before room stairs have natural smoke, think it has the natural smoke conditions, according to the specifications set mechanical smoke extraction facilities.
5. strategies
In view of the above problems, I think the Fire Department should be from the following aspects to strengthen building smoke facilities design and construction supervision:
1, should strengthen smoke facilities design and construction of business mentoring and training. Around the Fire Department for fire alarm and General Electric, fixed (automatic) fire-fighting facilities design and construction of business mentoring and training attaches great importance to the training process often overlooked smoke facilities design and construction professionals.
2. should implement smoke facilities construction by fire facilities construction unit of the system. Smoke management facilities is building automatic fire-fighting facilities, an important part, in accordance with the provisions of its construction by fire facilities construction units, but there are many items of smoke control facilities construction by air conditioning unit is responsible for the installation of construction professionals.
3, fire supervision departments of the examination staff at construction drawing examination, should focus on smoke control facilities design review should focus on the natural smoke exhaust window settings, window size, mechanical smoke extraction facilities set parts, fan selection, the air exhaust port settings, smoke partition until the review, while in construction should be strengthened to smoke the supervision and management of facilities, smoke control facilities as construction supervision and inspection of important content, make timely detection of problems, guidance, supervision and construction units for rectification.
Subscribe to: